DC Inverter Side Discharge VRF
Ⅱ
for North America
70
3.5 Fixing and damping of unit
The outdoor unit shall be fixed with 4 M12 bolts and closely contacted with the
foundation. Otherwise, big vibration and noise will be caused.
The outdoor unit shall be fixed firmly. The rubber board with thickness over 20mm or
corrugated rubber damping pad shall be applied between the unit and foundation.
3.6 Outline dimension and position of installation hole
When carrying the outdoor unit, hang the unit in four directions with two sufficient ropes.
In order to avoid excursion from the center, the angel of ropes must be smaller than 40º
during hanging and moving.
Unit:mm
(
inch
)
Model
A
B
C
D
E
GMV-36WL/A-T(U)
GMV-48WL/A-T(U
900
(
35-7/16
)
340
(
13-3/8
)
1345
(
53
)
572
(
22-1/2
)
378
(
15
)
GMV-60WL/A-T(U)
940
(37)
320
(12-9/16)
1430
(56-1/4)
632
(24-7/8)
350
(14-7/8)
3.7 Installation space requirement
If all sides of the ODU (including the top) are surrounded by walls, process according to
the following requirements for installation space:
Summary of Contents for GMV-36WL/A-T(U)
Page 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Page 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Page 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Page 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Page 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Page 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Page 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Page 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Page 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Page 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Page 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Page 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Page 131: ...JF00302320 ...