Page 76
Section 16: Product Fiche
Product fiche concerning the Commission Delegated Regulations
(EU)No 811/2013 of 18 February 2013
(EU)No 813/2013 of 2 August 2013
Models:
Outdoor
Unit:
Aerona³ HPID13R32
Indoor
Unit:
None
Air-to-water
heat
pump
Yes
Brine-to-water
heat
pump
No
Low
temperature
heat
pump
No
Equipped with a supplementary heater
No
Heat Pump Combination Heater
No
Parameters shall be declared for
Low-temperature applications
Parameters shall be declared for
Average Climate Conditions
Item
Symbol Value
Unit
Item
Symbol Value
Unit
Rated Heat Output (*)
Prated
10.0
kW
Seasonal Space Heating Efficiency
ƞs
215
%
Declared capacity for heating for part load at Indoor
Temperature 20°C and Outdoor Temperature Tj
Declared co-efficient of performance or primary energy ratio for
part load at Indoor temperature 20°C and Outdoor Temperatur Tj
Tj = -10°C
Pdh
10.0
kW
Tj = -10°C
COPd
2.90
Degredation co-efficient (**)
Cdh
0.99
-
Tj = -7°C
Pdh
9.6
kW
Tj = -7°C
COPd
3.03
Degredation co-efficient (**)
Cdh
0.99
-
Tj = +2°C
Pdh
6.10
kW
Tj = +2°C
COPd
6.20
Degredation co-efficient (**)
Cdh
0.99
-
Tj = +7°C
Pdh
4.30
kW
Tj = +7°C
COPd
8.50
Degredation co-efficient (**)
Cdh
0.98
-
Tj = +12°C
Pdh
4.10
kW
Tj = +12°C
COPd
10.30
Degredation co-efficient (**)
Cdh
0.99
-
Tj = bivalent temperature
Pdh
8.96
kW
Tj = bivalent temperature
COPd
3.01
Tj = Operation Limit Temperature
Pdh
7.70
kW
Tj = Operation Limit Temperature
COPd
2.98
Tj = -15°C (if TOL < -20°C)
Pdh
-
kW
Tj = -15°C (if TOL < -20°C)
COPd
-
Bivalent Temperature
Tbiv
-8
°C
Operation Limit Temperature
TOL
-10
°C
Heating water Operating Limit Temperature
WTOL
°C
Power consumption in modes other than active mode
Supplementary Heater
Off Mode
P
OFF
0.10
kW
Rate heat ouput
P
sup
0.00
kW
Thermostat-off mode
P
TO
0.04
kW
Standby mode
P
SB
0.10
kW
Type of energy input
Crankcase heater mode
P
CK
0.00
kW
Other items
Capacity Control
Variable
Rated airflow, outdoors
-
4464
m³/h
Sound Power Level (indoors/outdoors)
L
WA
39/61
dBA
Annual energy consumption
Q
HE
3794
kWh
For heat pump combination heater
Water heating energy efficiency
ƞwh
-
%
Declared load profile
-
-
-
Daily electricity consumption
Q
elec
-
kW/h
Annual electricity consumption
AEC
-
kW/h
*
For heat pumps, space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for
heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating
sup (Tj).
**
If Cdh is not determined by measurement then the default degredation coefficient is Cdh = 0.9.