Section 8: Operation
The heat pump operation for DHW production is controlled from
a remote contact, e.g. a cylinder thermostat or motorised valve
switch.
The remote ON/OFF DHW contact is enabled by parameter
5119. Refer to Table 8-8. The DHW mode cannot be controlled
automatically by the remote controller.
When DHW is turned ON by the remote contact and the heat pump
is ON it will start operation in DHW (comfort) mode.
DHW ON/OFF remote contact
Contact OPEN = DHW OFF
Contact CLOSE = DHW ON
(Comfort)
18
19
Terminal PCB
COM
DHW Remote
Contact
Figure 8-13:
ON/OFF DHW production remote contact
Table 8-8:
DHW ON/OFF contact parameters
Level
Parameter
Function description
Display and input value
Remarks
Group
Code
Default
Min.
Max.
Unit
I
31 01
DHW production priority setting
0=DHW is unavailable
1= DHW is available, and priority DHW over space heating
2= DHW is available, and priority space Heating over DHW
1
0
2
-
I
51 19
Terminal 19-18 : DHW remote contact
0=disable (Remote controller only)
1=enable
1
0
1
-
For details of how to access the parameter settings, refer to Section 9.3.
! NOTE !
In order to use DHW function, it is necessary to set
parameter 3101=1 and parameter 5119=1.
! NOTE !
Turn ON both remote controller using ON/OFF button, and
DHW ON/OFF remote contact to start heat pump for DHW.
! NOTE !
This volt free remote contact is provided by the Grant EP002
Interface relay box. Refer to Sections 6.8 and 6.10.
8.5
ON/OFF DHW PRODUCTION REMOTE CONTACT