Section 6: Electrical
Page 24
6.2
TERMINAL PCB INPUT/OUTPUT
Serial connections
Table 6-1:
Terminal PCB remote controller connections
Terminal
Function
Analogue Input
Digital Input
1 - 2 - 3
Remote controller
1=S1, 2=S2, 3=GND
Wire length is
maximum 100m with
1mm² shielded cables
Analogue/Digital INPUTS
Table 6-2:
Terminal PCB input/outputs
Terminal
Function
Analogue Input
Digital Input
19 - 18
DHW remote contact
Voltage free contact
12V10mA
20 - 21
Configurable input -ON/OFF remote contact
28 - 29*
Night mode - optional
30 - 31*
Low tariff - optional
* Requires external timer
For details of how to access the parameter settings, refer to Section 9.3.
Terminal block
Cable clamp
Connection diagrams
Unit side terminal
Power supply
Earth
N
)
L
(
)
N
(
1
2
3
Earth wire
Power supply cord
)
L
(
)
N
(
POWER
N
Do Not Use
Do Not Use
L
Figure 6-2:
Power supply
6.3
POWER SUPPLY
Use a dedicated power supply with a correctly sized circuit breaker.
The final power supply connection must be made from a
weatherproof lockable isolator located outside the building.
The cable should be either armoured or run in a flexible conduit
between the isolator and heat pump.