Device Description HG G-98780-A | English, Revision 16 | Date: 15.07.2021
24
Chapter 5 – Components and Operation
5.2.6.4.4 CAN Message Object 3 (D Identifier; Transmission Object)
For interpreting the values of Message Object 3 also refer to Table 8 on page 20. This
Message Object is used for commissioning, service and troubleshooting.
5.2.6.4.5 CAN Message Object 4 (Reference Transponder, transponder pro
-
gramming; Reception Object)
It is possible to activate and deactivate the reference transponder via the CAN bus.
For this it is necessary to send a Message Object with the same address as Message
Object 1 and a length of 5 bytes. The reference transponder may be de-/activated
via byte #5.
The programming of a transponder is initiated by setting byte #5 to the value 02. This
byte should be reset after 8 to 100 ms.
The programming of a transponder takes 100 to max. 200 ms. Afterwards the new
code is read and may be checked via Message Object 1. In case the programming
wasn‘t successful repeat the procedure.
5.2.6.5 Profibus
5.2.6.5.1 Profibus Input Bytes
Table 13
Structure of the CAN Message Object 3
Byte #
Length
Type
Description
1,2
2 Byte
Unsigned int
System status according to Table 9 on
page 21
3,4
2 Byte
Unsigned int
Lower 16 bit of the transponder code
5,6
2 Byte
Unsigned int
Sum voltage
7,8
2 Byte
Unsigned int
Number of code readings
Table 14
Structure of the CAN Message Object 4
Byte #
Length
Type
Description
1,2,3,4
4 Byte
Unsigned long
Transponder code to be programmed
(32 Bit)
5
1 Byte
Unsigned char
= 00: Reference transponder OFF
= 01: Reference transponder ON
= 02: Program Transponder
Table 15
Profibus Input Bytes (part 1 of 2)
Number of
Input Bytes Byte # Length
Type
Byte Sequence *) Description
6
1
2 Byte
Unsigned int
HiByte (LoByte)
System status in binary coding
2
LoByte (HiByte)
3
4 byte
Unsigned long HiByte (LoByte)
Transponder code
4
5
6
LoByte (HiByte)
7
7
1 Byte
Unsigned char
Supply voltage connected to
the antenna [x 100 mV]
8
8
1 Byte
Unsigned char
Current consumption [x 10 mA]