5.2.2.6
P(r)ofibus Parameter
In this menu the Profibus parameters can be altered.
ATTENTION!
If the Profibus is not connected or an antenna without Profibus is
used, it is strongly recommended to
deactivate
the Profibus, as
its activation causes transmission errors which lead to a reset of
the antenna!
Figure 21
Menu: Profibus parameters
Left, the bytes transmitted bytes to the master or the byte sent by the master are
shown. For further informations refer to Table 16 on page 29.
In the first line the profibus status is shown. It can have the folowing values:
Profibus Status Messages
NO_ERROR
Profibus active, no error
DPS2_INI_ERROR
Those messages indicate that the Profibus
hardware is missing or defunct
SPC_HW_ERROR
USER_IO_DATA_LEN
BUF_LEN_ERROR
Buffer length in master are wrong. Use the
official GSD file to fix this (see section D on
page 49)
PB_OFFLINE
No contact with master
Table 17
Possible Profibus Status Messages
Byte # Master-Input Profibus-Status: PB_OFFLINE
0 00
1 00
2 00
3 00
4 00
5 00
6 e7
7 18
8 00 (P)rofibus active YES
9 00 (A)ddress: [0..125]: 2
10 00 (O)rder of Data Transfer (0= HiByte first): 0
11 00
12 00 (Q)uit Menue
13 00
14 00
15 00
Byte # Master-Output
0 00