4.3. ALARM CONDITIONS
Here is a list of the possible alarms and their meaning:
►
FREE RUNNING
:
The server has been forced in autonomous operating mode. No time
input is used for synchronization. Useful for test purposes.
►
NO TIME CODE !
The Time inputs of the server are not synchronized. (GPS signal not
received, no NTP server available,...)
►
AUTONOMY CRITICAL !
: There is no synchronization source, and the server is about
to switch the outputs OFF (3 min autonomy left).
►
NEVER SYNC !
: The server has been powered for at least 15 minute, and there is still
no valid synchronization source available.
►
ETHERNET LINK ERROR
: There is a problem with the network cable connection.
►
OUTPUT ALARM !
: One or several of the output cards are not detected by the main
control card. The status of the output cards can be checked on the Web page in the
“Output” tab. This can happen on occasions during initializing and in normal opera-
ting. If the problem persists and the corresponding outputs no longer broadcast time
codes, please contact Gorgy Timing Customers’ Service.
►
SERVER LOCKED
: The time outputs have been deactivated by a user.
►
SYNC ALARM!
: There is no time source available and the server no longer has
battery.
►
SECURITY LOCKDOWN!
: The configuration interfaces are locked for 5 minutes
following 3 authentication failures.