background image

11

P

IPInG

IMPoRtant notE: t

o

 

avoId

 

PoSSIblE

 

UnSatISfactoRy

 

oPERatIon

 

oR

 

EqUIPMEnt

 

daMaGE

 

dUE

 

to

 

UndER

 

fIRInG

 

of

 

EqUIPMEnt

do

 

not

 

UndERSIZE

 

tHE

 

natURal

/

PRoPanE

 

GaS

 

PIPInG

 

fRoM

 

tHE

 

MEtER

/

tank

 

to

 

tHE

 

UnIt

W

HEn

 

SIZInG

 

a

 

tRUnk

 

lInE

InclUdE

 

all

 

aPPlIancES

 

on

 

tHat

 

lInE

 

tHat

 

coUld

 

bE

 

oPERatEd

 

SIMUltanEoUSly

.

The gas line installation must comply with local codes, or 

in the absence of local codes, with the latest edition of the 

National Fuel Gas Code NFPA 54 / ANSI Z223.1.

n

atURal

 G

aS

 c

onnEctIon

1/2

3/4

1

1  1/4

1  1 /2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

Pressure= .50 PSIG or less and Pressure Drop of 0.3" W.C.
(Based on 0.60 Specific Gravity Gas)

Natural Gas Capacity of Pipe

in Cubic Feet of Gas Per Hour (CFH)

Nominal Black Pipe Size (inches)

Length of

Pipe in Feet

Heating Value of Gas (BTU/Cubic Foot

CFH = 

BTUH Furnace Input

Refer to the Proper Piping Practice drawing for the general 

layout at the unit. The following rules apply: 

1. 

Use black iron pipe and fittings for the supply piping.  

The use of a flex connector and/or copper piping is 

permitted  as long as it is in agreement with local 

codes.

2.  Use pipe joint compound on male threads only. Pipe 

joint compound must be resistant to the action of the 

fuel used. 

3.  Use ground joint unions. 

4.  Install a drip leg to trap dirt and moisture before it can 

enter the gas valve. The drip leg must be a minimum 

of three inches long.

5.  Use two pipe wrenches when making connection to 

the gas valve to keep it from turning.

6.  Install a manual shut-off valve in a convenient location 

(within six feet of unit) between the meter and the unit.

7.  Tighten all joints securely.

8.  The unit must be connected to the building piping by 

one of the following methods:

• 

 Rigid metallic pipe and fittings

• 

 Semirigid metallic tubing and metallic fittings 

(Aluminum alloy tubing must not be used in 

exterior locations).

•   Listed gas appliance connectors used in 

accordance with the terms of their listing 

that are completely in the same room as the 

equipment. Always use a new listed connector.

•  In the prior two methods above the connector 

or tubing must be protected from physical 

and thermal damage. Aluminum alloy tubing 

and connectors must be coated to protect 

against external corrosion when in contact with 

masonry, plaster or insulation or are subject to 

repeated wettings by liquids (water - not rain 

water, detergents or sewage).

BURNER

DOOR

DRIP

LEG

MANUAL

SHUT-OFF

GROUND JOINT

UNION

TBD

P

RoPER

 

PIPInG

 

PRactIcE

 

notE:  t

HE

 

UnIt

 

GaS

 

SUPPly

 

EntRancE

 

IS

 

factoRy

 

SEalEd

 

WItH

 

PlUGS

.  k

EEP

 

PlUGS

 

In

 

PlacE

 

UntIl

 

GaS

 

SUPPly

 

IS

 

REady

 

to

 

bE

 

InStallEd

.  o

ncE

 

REady

REPlacE

 

tHE

 

PlUGS

 

WItH

 

tHE

 

SUPPlIEd

 

GRoMMEtS

 

and

 

InStall

 

GaS

 

SUPPly

 

lInE

.

Summary of Contents for GPG16 M Series

Page 1: ...ING This forced air central unit design complies with requirements embodied in The American National Standard National Standard of Canada ANSI Z21 47 CSA 2 3 Gas fired central furnaces WARNING PROP 65...

Page 2: ...any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot...

Page 3: ...ese installation and operating instructions all local building codes and ordinances or in their absence with the latest edition of the National Fuel Gas Code NFPA54 ANSI Z223 1 and National Standard o...

Page 4: ...g material according to local codes Pre Installation Checks Carefully read all instructions for the installation prior to installing unit Ensure each step or procedure is understood and any special co...

Page 5: ...ngs building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 Minimum horizontal clearance of 48 from the furnace...

Page 6: ...ir into the unit fresh air intake NOTE If the 36 minimum clearance is used on the control panel side of unit a flue extension kit needs be to installed to prevent flue gas recirculation See table belo...

Page 7: ...the unit must not be less than 60 Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in...

Page 8: ...ng from sharp edges follow national electrical code and all local codes and ordinances Do not route wires through removable access panels CAUTION Conduit and fittings must be weather tight to prevent...

Page 9: ...k connections control box note depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with exces...

Page 10: ...efer to unit wiring diagrams for thermostat or remote sensor connections GAS SUPPLY PIPING WARNING To prevent personal injury or death due to improper installation adjustment alteration service or mai...

Page 11: ...threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint unions 4 Install a drip leg to trap dirt and moisture before it can enter the gas valve The drip le...

Page 12: ...to convert units to propane gas NOx screens must be removed before converting to LP Remove burner assembly and pull NOx screens from each burner tube When all the screens are out reassemble the burner...

Page 13: ...supply gas pressure is less than 11 0 w c or greater than 13 0 w c 6 All pipe connections should be sealed with a pipe thread compound which is resistant to the fuel used with the furnace A soapy wat...

Page 14: ...Checks procedure provides a step by step sequence which if followed will assure the proper startup of the equipment in the minimum amount of time Air balancing of duct system is not considered part o...

Page 15: ...Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the terminal block TB1 Refer to Appendix A for blower performance at each speed tap Refer to Appendix D for maxi...

Page 16: ...16 Wiring Example...

Page 17: ...rmal manifold pressure for High fire is 3 5 w c on natural gas and 10 0 w c for propane gas Low fire natural gas 2 0 w c 6 0 w c low fire propane gas Minimum gas supply pressure is 5 0 w c for natural...

Page 18: ...Gas Only Check It is the responsibility of the contractor to adjust the gas input to the unit To measure the gas input use a gas meter and proceed as follows 1 Turn off gas supply to all other applian...

Page 19: ...speed will lower the temperature rise A slower blower speed will increase the temperature rise NOTE Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the...

Page 20: ...prior to resetting this manual reset control WARNING To avoid property damage personal injury or death due to fire or explosion a qualified servicer must investigate the reason for the rollout protec...

Page 21: ...the compressor control circuits will be ready to respond to a subsequent call for cooling Refrigeration Performance Check Check that compressor RLA corresponds to values shown in Appendix B RLA draw c...

Page 22: ...remove the filter access panel on return side of the unit Cabinet Finish Maintenance Use a fine grade automotive wax on the cabinet finish to maintain the finish s original high luster This is especi...

Page 23: ...dicates an internal fault check power supply to unit for proper voltage check all fuses circuit breakers and wiring Disconnect electric power for five seconds If LED remains off after restoring power...

Page 24: ...ce 4 FLASH CODE If the primary limit switch opens the gas valve is immediately deenergized the induced draft and air circulating blowers are energized The induced draft and air circulator blowers rema...

Page 25: ...62 859 0 62 0 2 1901 912 0 66 0 4 1787 909 0 66 0 4 1824 966 0 70 0 6 1702 955 0 69 0 6 1737 1014 0 73 0 8 1625 1005 0 73 0 8 1658 1067 0 77 0 2 2132 954 0 91 0 2 2175 1014 0 97 0 4 2056 993 0 95 0 4...

Page 26: ...4 70 0 70 0 7 2 6 5 50 6 49 9 70 0 70 0 Power Supply Model Number Electrical Rating Compressor Outdoor Fan Motor Indoor Fan Motor Optional Electric Heat Optional Powered Convienience Outlet FLA Optio...

Page 27: ...CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal...

Page 28: ...28 APPENDIX D MIN MAX AIRFLOW UNIT HEAT RANGE HIGH FIRE RATE BTU HR HEATING MINIMUM SCFM COOLING MINIMUM SCFM MAXIMUM SCFM GPG1660140M41 HIGH 140 000 1615 1500 2500 AIR FLOW RANGE FOR HIGH STAGE...

Page 29: ...RD YL YL BL VMC A1 A2 LS RD RD BK BK YL YL BK BK PU PU BK BK RS BK BK BK BK LPS ALS GAS PLM GAS PLF GR GY PU PU BL BR TN PU PU PU BL BR TN VM L1 L2 T1 T2 VMC F3 F3 FB3 4 BK RD PK BL BR GR YL WH PU GR...

Page 30: ...30...

Page 31: ...31...

Page 32: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Reviews: