background image

14

Install condensate drain trap as shown. Use 3/4” drain line 

and fittings or larger. Do not operate without trap. 

H

oRIZontal

 d

RaIn

 

Drainage of condensate directly onto the roof may be 

acceptable; refer to local code. It is recommended that a 

small drip pad of either stone, mortar, wood or metal be 

provided to prevent any possible damage to the roof. 

v

ERtIcal

 d

RaIn

To use the bottom drain connection, remove the drain plug 

from the bottom connection and install it in the horizontal 

connection.

c

lEanInG

Due to the fact that drain pans in any air conditioning 

unit will have some moisture in them, algae and fungus 

will grow due to airborne bacteria and spores. Periodic 

cleaning is necessary to prevent this build-up from plugging 

the drain.

STARTUP, ADJUSTMENTS, AND CHECKS

WARNING

HIGH voltaGE!

t

o

 

avoId

 

PERSonal

 

InjURy

 

oR

 

dEatH

 

dUE

 

to

 

ElEctRIcal

 

SHock

bond

 

tHE

 

fRaME

 

of

 

tHIS

 

UnIt

 

to

 

tHE

 

bUIldInG

 

ElEctRIcal

 

GRoUnd

 

by

 

USE

 

of

 

tHE

 

GRoUndInG

 

tERMInal

 

PRovIdEd

 

oR

 

otHER

 

accEPtablE

 

MEanS

. d

ISconnEct

 

all

 

PoWER

 

bEfoRE

 

SERvIcInG

 

oR

 

InStallInG

 

tHIS

 

UnIt

.

P

RE

-S

taRtUP

 I

nStRUctIonS

 - G

EnERal

 

CAUTION

t

o

 

PREvEnt

 

PRoPERty

 

daMaGE

 

oR

 

PERSonal

 

InjURy

do

 

not

 

StaRt

 

tHE

 

UnIt

 

UntIl

 

all

 

nEcESSaRy

 

PRE

-

cHEckS

 

and

 

tEStS

 

HavE

 

bEEn

 

PERfoRMEd

.

Prior to the beginning of Startup, Adjustments, and Checks 

procedures, the following steps should be completed in the 

building.

WARNING

MovInG MacHInERy HaZaRd!

t

o

 

PREvEnt

 

PoSSIblE

 

PERSonal

 

InjURy

 

oR

 

dEatH

dISconnEct

 

PoWER

 

to

 

tHE

 

UnIt

 

and

 

Padlock

 

In

 

tHE

 

“off” 

PoSItIon

 

bEfoRE

 

SERvIcInG

 

fanS

.

This unit is equipped with an electronic ignition device to 

automatically light the main burners. It also has a power 

vent blower to exhaust combustion products.

On new installations, or if a major component has been 

replaced, the operation of the unit must be checked.

Check unit operation as outlined in the following 

instructions. If any sparking, odors, or unusual sounds 

are encountered, shut off electrical power and recheck for 

wiring errors, or obstructions in or near the blower motors. 

Duct covers must be removed before operating unit.

The Startup, Adjustments, and Checks procedure provides 

a step-by-step sequence which, if followed, will assure the 

proper startup of the equipment in the minimum amount of 

time. Air balancing of duct system is not considered part 

of this procedure. However, it is an important phase of any 

air conditioning system startup and should be performed 

upon completion of the Startup, Adjustments, and Checks 

procedure. The Startup, Adjustments, and Checks 

procedure at outside ambients below 55°F should be 

limited to a readiness check of the refrigeration system with 

the required final check and calibration left to be completed 

when the outside ambient rises above 55°F.

t

EMPoRaRy

 H

EatInG

 o

R

 c

oolInG

If the unit is to be used for temporary heating or cooling, a 

“Startup, Adjustments, and Checks” must first be performed 

in accordance with this manual. Damage or repairs due to 

failure to comply with these requirments are not covered 

under the warranty. 

After 

the machines are used for 

temporary heating or cooling, inspect the coils, fans, and 

motors for unacceptable levels of construction dust and dirt 

and install new filters.

c

ontRactoR

 R

ESPonSIbIlIty

The installing contractor must be certain that:

•   All supply and return air ductwork is in place, properly 

sealed, and corresponds with installation instructions.

•   All thermostats are mounted and wired in accordance 

with installation instructions.

•   All electric power, all gas, hot water or steam line 

connections, and the condensate drain installation 

have been made to each unit on the job. These 

main supply lines must be functional and capable of 

operating all units simultaneously.

•   Requirements are met for venting and combution air.

• 

  Air filters are in place.

•   Input rate and temperature rise are adjusted per rating 

plate.

R

oof

 c

URb

 I

nStallatIon

 c

HEck

Inspect the roof curb for correct installation. The unit and 

curb assembly should be level. Inspect the flashing of the 

roof mounting curb to the roof, especially at the corners, for 

good workmanship. Also check for leaks around gaskets. 

Note any deficiencies in a separate report and forward to 

the contractor. 

o

bStRUctIonS

, f

an

 c

lEaRancE

 

and

 W

IRInG

Remove any extraneous construction and shipping 

materials that may be found during this procedure.  Rotate 

all fans manually to check for proper clearances and that 

Summary of Contents for GPG16 M Series

Page 1: ...ING This forced air central unit design complies with requirements embodied in The American National Standard National Standard of Canada ANSI Z21 47 CSA 2 3 Gas fired central furnaces WARNING PROP 65...

Page 2: ...any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot...

Page 3: ...ese installation and operating instructions all local building codes and ordinances or in their absence with the latest edition of the National Fuel Gas Code NFPA54 ANSI Z223 1 and National Standard o...

Page 4: ...g material according to local codes Pre Installation Checks Carefully read all instructions for the installation prior to installing unit Ensure each step or procedure is understood and any special co...

Page 5: ...ngs building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 Minimum horizontal clearance of 48 from the furnace...

Page 6: ...ir into the unit fresh air intake NOTE If the 36 minimum clearance is used on the control panel side of unit a flue extension kit needs be to installed to prevent flue gas recirculation See table belo...

Page 7: ...the unit must not be less than 60 Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in...

Page 8: ...ng from sharp edges follow national electrical code and all local codes and ordinances Do not route wires through removable access panels CAUTION Conduit and fittings must be weather tight to prevent...

Page 9: ...k connections control box note depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with exces...

Page 10: ...efer to unit wiring diagrams for thermostat or remote sensor connections GAS SUPPLY PIPING WARNING To prevent personal injury or death due to improper installation adjustment alteration service or mai...

Page 11: ...threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint unions 4 Install a drip leg to trap dirt and moisture before it can enter the gas valve The drip le...

Page 12: ...to convert units to propane gas NOx screens must be removed before converting to LP Remove burner assembly and pull NOx screens from each burner tube When all the screens are out reassemble the burner...

Page 13: ...supply gas pressure is less than 11 0 w c or greater than 13 0 w c 6 All pipe connections should be sealed with a pipe thread compound which is resistant to the fuel used with the furnace A soapy wat...

Page 14: ...Checks procedure provides a step by step sequence which if followed will assure the proper startup of the equipment in the minimum amount of time Air balancing of duct system is not considered part o...

Page 15: ...Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the terminal block TB1 Refer to Appendix A for blower performance at each speed tap Refer to Appendix D for maxi...

Page 16: ...16 Wiring Example...

Page 17: ...rmal manifold pressure for High fire is 3 5 w c on natural gas and 10 0 w c for propane gas Low fire natural gas 2 0 w c 6 0 w c low fire propane gas Minimum gas supply pressure is 5 0 w c for natural...

Page 18: ...Gas Only Check It is the responsibility of the contractor to adjust the gas input to the unit To measure the gas input use a gas meter and proceed as follows 1 Turn off gas supply to all other applian...

Page 19: ...speed will lower the temperature rise A slower blower speed will increase the temperature rise NOTE Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the...

Page 20: ...prior to resetting this manual reset control WARNING To avoid property damage personal injury or death due to fire or explosion a qualified servicer must investigate the reason for the rollout protec...

Page 21: ...the compressor control circuits will be ready to respond to a subsequent call for cooling Refrigeration Performance Check Check that compressor RLA corresponds to values shown in Appendix B RLA draw c...

Page 22: ...remove the filter access panel on return side of the unit Cabinet Finish Maintenance Use a fine grade automotive wax on the cabinet finish to maintain the finish s original high luster This is especi...

Page 23: ...dicates an internal fault check power supply to unit for proper voltage check all fuses circuit breakers and wiring Disconnect electric power for five seconds If LED remains off after restoring power...

Page 24: ...ce 4 FLASH CODE If the primary limit switch opens the gas valve is immediately deenergized the induced draft and air circulating blowers are energized The induced draft and air circulator blowers rema...

Page 25: ...62 859 0 62 0 2 1901 912 0 66 0 4 1787 909 0 66 0 4 1824 966 0 70 0 6 1702 955 0 69 0 6 1737 1014 0 73 0 8 1625 1005 0 73 0 8 1658 1067 0 77 0 2 2132 954 0 91 0 2 2175 1014 0 97 0 4 2056 993 0 95 0 4...

Page 26: ...4 70 0 70 0 7 2 6 5 50 6 49 9 70 0 70 0 Power Supply Model Number Electrical Rating Compressor Outdoor Fan Motor Indoor Fan Motor Optional Electric Heat Optional Powered Convienience Outlet FLA Optio...

Page 27: ...CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal...

Page 28: ...28 APPENDIX D MIN MAX AIRFLOW UNIT HEAT RANGE HIGH FIRE RATE BTU HR HEATING MINIMUM SCFM COOLING MINIMUM SCFM MAXIMUM SCFM GPG1660140M41 HIGH 140 000 1615 1500 2500 AIR FLOW RANGE FOR HIGH STAGE...

Page 29: ...RD YL YL BL VMC A1 A2 LS RD RD BK BK YL YL BK BK PU PU BK BK RS BK BK BK BK LPS ALS GAS PLM GAS PLF GR GY PU PU BL BR TN PU PU PU BL BR TN VM L1 L2 T1 T2 VMC F3 F3 FB3 4 BK RD PK BL BR GR YL WH PU GR...

Page 30: ...30...

Page 31: ...31...

Page 32: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Reviews: