background image

10

4-1/2"

47-9/16"

7-1/2"

4-1/16 DIA.

POWER THRU

THE CURB

RETURN

19-3/8

31-3/8

LOW VOLTAGE

ENTRANCE

HIGH VOLTAGE ENTRANCE

(REMOVE PLUG)

ElEctRIcal

 

EntRancE

 

and

 

tHRU

 

cURb

(

bottoM

 

vIEW

 

of

 

UnIt

l

oW

 v

oltaGE

 c

ontRol

 W

IRInG

 

1.  A 24V thermostat must be installed for unit operation. 

2.  Locate thermostat or remote sensor in the conditioned 

space where it will sense average temperature. Do 

not locate the device where it may be directly exposed 

to supply air, sunlight or other sources of heat. Follow 

installation instructions packaged with the thermostat.

3.  Use #18 AWG wire for 24V control wiring runs not 

exceeding 75 feet. Use #16 AWG wire for 24V control 

wiring runs not exceeding 125 feet. Use #14 AWG 

wire for 24V control wiring runs not exceeding 200 

feet. Low voltage wiring may be National Electrical 

Code (NEC) Class 2 where permitted by local codes.

4.  Route thermostat wires from sub-base terminals 

to the unit. Control wiring should enter through the 

condenser panel opening or through curb indicated in 

“Electrical Entrance” figure. Connect thermostat and 

any accessory wiring to low voltage terminal block 

TB1 in the main control box.

5.  For two-stage heating operation, remove the factory 

installed jumper connecting W1 and W2 terminals on 

terminal block.

notE:  f

IEld

-

SUPPlIEd

 

condUIt

 

May

 

nEEd

 

to

 

bE

 

InStallEd

 

dEPEndInG

 

on

 

UnIt

/

cURb

 

confIGURatIon

U

SE

 #18 aWG 

SolId

 

condUctoR

 

WIRE

 

WHEnEvER

 

connEctInG

 

tHERMoStat

 

WIRES

 

to

 

tERMInalS

 

on

 

SUb

-

baSE

. do not 

USE

 

laRGER

 

tHan

 #18 aWG 

WIRE

. a 

tRanSItIon

 

to

 #18 aWG 

WIRE

 

May

 

bE

 

REqUIREd

 

bEfoRE

 

EntERInG

 

tHERMoStat

 

SUb

-

baSE

 

notE: R

EfER

 

to

 

UnIt

 

WIRInG

 

dIaGRaMS

 

foR

 

tHERMoStat

 

oR

 

REMotE

 

SEnSoR

 

connEctIonS

.

GAS SUPPLY PIPING 

WARNING

t

o

 

PREvEnt

 

PERSonal

 

InjURy

 

oR

 

dEatH

 

dUE

 

to

 

IMPRoPER

 

InStallatIon

adjUStMEnt

altERatIon

SERvIcE

 

oR

 

MaIntEnancE

REfER

 

to

 

tHIS

 

ManUal

f

oR

 

addItIonal

 

aSSIStancE

 

oR

 

InfoRMatIon

conSUlt

 

a

 

qUalIfIEd

 

InStallER

SERvIcER

 

aGEncy

 

oR

 

tHE

 

GaS

 

SUPPlIER

IMPoRtant notE: t

HIS

 

UnIt

 

IS

 

factoRy

 

SEt

 

to

 

oPERatE

 

on

 

natURal

 

GaS

 

at

 

tHE

 

altItUdES

 

SHoWn

 

on

 

tHE

 

RatInG

 

PlatE

WARNING

t

o

 

avoId

 

PRoPERty

 

daMaGE

PERSonal

 

InjURy

 

oR

 

dEatH

 

WHEn

 

EItHER

 

USInG

 

PRoPanE

 

GaS

 

alonE

 

oR

 

at

 

HIGHER

 

altItUdES

obtaIn

 

and

 

InStall

 

tHE

 

PRoPER

 

convERSIon

 

kIt

(

S

). f

aIlURE

 

to

 

do

 

So

 

can

 

RESUlt

 

In

 

UnSatISfactoRy

 

oPERatIon

 

and

/

oR

 

EqUIPMEnt

 

daMaGE

. H

IGH

 

altItUdE

 

kItS

 

aRE

 

foR

 U.S. 

InStallatIonS

 

only

 

and

 

aRE

 

not

 

aPPRovEd

 

foR

 

USE

 

In

 c

anada

The rating plate is stamped with the model number, type of 

gas and gas input rating. Make sure the unit is equipped 

to operate on the type of gas available. Conversion to 

propane (LP) gas is permitted with the use of the factory 

authorized conversion kit (see the unit Technical Manual for 

the appropriate kit). For High Altitude derates, refer to the 

latest edition of the National Fuel Gas Code NFPA 54/ANSI 

Z223.1 or National Standard of Canada, Natural Gas and 

Propane Installation Code, CSA B149.1.

NATURAL

Min.   5.0" W.C., Max. 10.0" W.C.

PROPANE

Min. 11.0" W.C., Max. 14.0" W.C.

INLET GAS PRESSURE

InlEt

 

GaS

 

PRESSURE

 

MUSt

 

not

 

ExcEEd

 

MaxIMUM

 

valUE

 

SHoWn

 

In

 

tablE

 

abovE

The minimum supply pressure should not vary from that 

shown in the table above because this could prevent the 

unit from having dependable ignition. In addition, gas input 

to the burners must not exceed the rated input shown 

on the rating plate. Overfiring of the unit could result in 

premature heat exchanger failure.

Summary of Contents for GPG16 M Series

Page 1: ...ING This forced air central unit design complies with requirements embodied in The American National Standard National Standard of Canada ANSI Z21 47 CSA 2 3 Gas fired central furnaces WARNING PROP 65...

Page 2: ...any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot...

Page 3: ...ese installation and operating instructions all local building codes and ordinances or in their absence with the latest edition of the National Fuel Gas Code NFPA54 ANSI Z223 1 and National Standard o...

Page 4: ...g material according to local codes Pre Installation Checks Carefully read all instructions for the installation prior to installing unit Ensure each step or procedure is understood and any special co...

Page 5: ...ngs building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 Minimum horizontal clearance of 48 from the furnace...

Page 6: ...ir into the unit fresh air intake NOTE If the 36 minimum clearance is used on the control panel side of unit a flue extension kit needs be to installed to prevent flue gas recirculation See table belo...

Page 7: ...the unit must not be less than 60 Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in...

Page 8: ...ng from sharp edges follow national electrical code and all local codes and ordinances Do not route wires through removable access panels CAUTION Conduit and fittings must be weather tight to prevent...

Page 9: ...k connections control box note depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with exces...

Page 10: ...efer to unit wiring diagrams for thermostat or remote sensor connections GAS SUPPLY PIPING WARNING To prevent personal injury or death due to improper installation adjustment alteration service or mai...

Page 11: ...threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint unions 4 Install a drip leg to trap dirt and moisture before it can enter the gas valve The drip le...

Page 12: ...to convert units to propane gas NOx screens must be removed before converting to LP Remove burner assembly and pull NOx screens from each burner tube When all the screens are out reassemble the burner...

Page 13: ...supply gas pressure is less than 11 0 w c or greater than 13 0 w c 6 All pipe connections should be sealed with a pipe thread compound which is resistant to the fuel used with the furnace A soapy wat...

Page 14: ...Checks procedure provides a step by step sequence which if followed will assure the proper startup of the equipment in the minimum amount of time Air balancing of duct system is not considered part o...

Page 15: ...Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the terminal block TB1 Refer to Appendix A for blower performance at each speed tap Refer to Appendix D for maxi...

Page 16: ...16 Wiring Example...

Page 17: ...rmal manifold pressure for High fire is 3 5 w c on natural gas and 10 0 w c for propane gas Low fire natural gas 2 0 w c 6 0 w c low fire propane gas Minimum gas supply pressure is 5 0 w c for natural...

Page 18: ...Gas Only Check It is the responsibility of the contractor to adjust the gas input to the unit To measure the gas input use a gas meter and proceed as follows 1 Turn off gas supply to all other applian...

Page 19: ...speed will lower the temperature rise A slower blower speed will increase the temperature rise NOTE Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the...

Page 20: ...prior to resetting this manual reset control WARNING To avoid property damage personal injury or death due to fire or explosion a qualified servicer must investigate the reason for the rollout protec...

Page 21: ...the compressor control circuits will be ready to respond to a subsequent call for cooling Refrigeration Performance Check Check that compressor RLA corresponds to values shown in Appendix B RLA draw c...

Page 22: ...remove the filter access panel on return side of the unit Cabinet Finish Maintenance Use a fine grade automotive wax on the cabinet finish to maintain the finish s original high luster This is especi...

Page 23: ...dicates an internal fault check power supply to unit for proper voltage check all fuses circuit breakers and wiring Disconnect electric power for five seconds If LED remains off after restoring power...

Page 24: ...ce 4 FLASH CODE If the primary limit switch opens the gas valve is immediately deenergized the induced draft and air circulating blowers are energized The induced draft and air circulator blowers rema...

Page 25: ...62 859 0 62 0 2 1901 912 0 66 0 4 1787 909 0 66 0 4 1824 966 0 70 0 6 1702 955 0 69 0 6 1737 1014 0 73 0 8 1625 1005 0 73 0 8 1658 1067 0 77 0 2 2132 954 0 91 0 2 2175 1014 0 97 0 4 2056 993 0 95 0 4...

Page 26: ...4 70 0 70 0 7 2 6 5 50 6 49 9 70 0 70 0 Power Supply Model Number Electrical Rating Compressor Outdoor Fan Motor Indoor Fan Motor Optional Electric Heat Optional Powered Convienience Outlet FLA Optio...

Page 27: ...CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal...

Page 28: ...28 APPENDIX D MIN MAX AIRFLOW UNIT HEAT RANGE HIGH FIRE RATE BTU HR HEATING MINIMUM SCFM COOLING MINIMUM SCFM MAXIMUM SCFM GPG1660140M41 HIGH 140 000 1615 1500 2500 AIR FLOW RANGE FOR HIGH STAGE...

Page 29: ...RD YL YL BL VMC A1 A2 LS RD RD BK BK YL YL BK BK PU PU BK BK RS BK BK BK BK LPS ALS GAS PLM GAS PLF GR GY PU PU BL BR TN PU PU PU BL BR TN VM L1 L2 T1 T2 VMC F3 F3 FB3 4 BK RD PK BL BR GR YL WH PU GR...

Page 30: ...30...

Page 31: ...31...

Page 32: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Reviews: