background image

20

9.  Integrated ignition control will close its normally open 

contacts after a delay of approximately 30 seconds. 

This action energizes the blower motor contactor and 

starts the supply fan motor. Operation of the supply 

fan circulates air across the heat exchanger and 

delivers heated air to the conditioned space.

10. When the space temperature rises, the thermostat 

will open R-W. Opening R-W will cause the gas valve 

to close, and the furnace to shut down.

11. The furnace has three high temperature limit controls, 

which can shut down the burner. They do not shut 

down the venter motor.

U

nIt

 S

HUtdoWn

1.  Set the room heating setpoint to lowest setting.

2.  Turn off the electrical power supply to the unit.

3.  Remove the heat exchanger door on the side of the 

unit by removing screws.

4.  Move the gas control valve switch to the OFF position.

5.  Close manual gas shut off valve external to the unit.

6.  Replace the heat exchanger door on the unit.

7.  If cooling and/or air circulation will be  desired, turn 

ON gas control valve switch and the electrical power.

a

UtoMatIc

 R

ESEt

 H

IGH

 l

IMIt

 c

ontRol

 (lS)

Located in the burner compartment on the heat exchanger, 

its sensing element projects through the blower section 

bulkhead and senses the temperature at the rear of the 

furnace. It will cycle the furnace off if the temperature 

exceeds 100°F plus maximum rise.

a

UxIlIaRy

 H

IGH

 l

IMIt

 c

ontRol

 (alS)

Located in the blower compartment on the blower housing, 

it senses air temperature within the blower compartment 

and  protects the filters from excessive temperature. It will 

shut down the furnace if it senses excessive temperatures.

Elevated temperatures at the control are normally caused 

by blower failure. The reason for the shut down should be 

determined and repaired prior to resetting.

M

anUal

 R

ESEt

 f

laME

 R

olloUt

 c

ontRol

 (RS)

Located in the burner compartment at the top of the burner 

assembly, it senses high temperature that could occur if 

the heat exchanger tubes were plugged and the flame was 

rolling out instead of entering the tubes. It has a manual 

push-button reset that cannot be actuated until the limit 

control has cooled.

The reason for elevated temperatures at the control should 

be determined and repaired prior to resetting this manual 

reset control.

WARNING

t

o

 

avoId

 

PRoPERty

 

daMaGE

PERSonal

 

InjURy

 

oR

 

dEatH

 

dUE

 

to

 

fIRE

 

oR

 

ExPloSIon

a

 

qUalIfIEd

 

SERvIcER

 

MUSt

 

InvEStIGatE

 

tHE

 

REaSon

 

foR

 

tHE

 

RolloUt

 

PRotEctIon

 

dEvIcE

 

to

 

oPEn

 

bEfoRE

 

ManUally

 

RESEttInG

 

tHE

 

RolloUt

 

PRotEctIon

 

dEvIcE

R

EfRIGERatIon

 S

yStEM

 c

HEckS

This unit is equipped with thermal expansion valves. 

Ensure the hold-down bolts on the compressor are secure 

and have not vibrated loose during shipment.  Check 

that the vibration grommets have been installed and 

visually check all piping for damage and leaks and repair 

if necessary.  The entire system has been factory charged 

and tested, making it unnecessary to field charge.  Factory 

refrigerant charge is shown on the unit’s nameplate.

To confirm charge levels or, if a leak occurs and charge 

needs to be added to the system, it is recommended to 

evacuate the system and recharge refrigerant to the unit’s 

nameplate specifications.  This unit has been rated in the 

cooling mode at the AHRI rated conditions of:  indoor (80°F 

db/67°F wb) and outdoor (95°F db).  While operating at this 

condition, the superheat should range from 9°F to 11°F for 

each refrigeration circuit measured at the suction service 

port located near the compressor.

S

taRt

-U

P

 P

RocEdURE

 

and

 c

HEcklISt

Begin with power turned off at all disconnects.

1.  Turn thermostat system switch to “Cool,” and fan 

switch to “Auto” and turn temperature setting as high 

as it will go.

2.  Inspect all registers and set them to the normal open 

position.

3.  Turn on the electrical supply at the disconnect.
4.  Turn the fan switch to the “ON” position. The blower 

should operate after a 7 second delay.

5.  Turn the fan switch to “Auto” position. The blower 

should stop after a 60 second delay.

6.  Slowly lower the cooling temperature until the unit 

starts. The compressor, blower and fan should now be 

operating. Allow the unit to run 10 minutes, make sure 

cool air is being supplied by the unit.

7.  Turn the temperature setting to the highest position, 

stopping the unit. The indoor blower will continue to 

run for 60 seconds.

8.  Turn the thermostat system switch to “OFF” and 

disconnect all power when servicing the unit. 

R

EfRIGERatIon

 S

EqUEncE

 c

HEck

1.  24VAC control voltage is provided by the control 

transformer to terminal XS. The control voltage is 

passed through any installed safety shutdown devices 

such as the smoke detector before providing 24VAC 

to terminals ES and R. 

Summary of Contents for GPG16 M Series

Page 1: ...ING This forced air central unit design complies with requirements embodied in The American National Standard National Standard of Canada ANSI Z21 47 CSA 2 3 Gas fired central furnaces WARNING PROP 65...

Page 2: ...any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot...

Page 3: ...ese installation and operating instructions all local building codes and ordinances or in their absence with the latest edition of the National Fuel Gas Code NFPA54 ANSI Z223 1 and National Standard o...

Page 4: ...g material according to local codes Pre Installation Checks Carefully read all instructions for the installation prior to installing unit Ensure each step or procedure is understood and any special co...

Page 5: ...ngs building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 Minimum horizontal clearance of 48 from the furnace...

Page 6: ...ir into the unit fresh air intake NOTE If the 36 minimum clearance is used on the control panel side of unit a flue extension kit needs be to installed to prevent flue gas recirculation See table belo...

Page 7: ...the unit must not be less than 60 Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in...

Page 8: ...ng from sharp edges follow national electrical code and all local codes and ordinances Do not route wires through removable access panels CAUTION Conduit and fittings must be weather tight to prevent...

Page 9: ...k connections control box note depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with exces...

Page 10: ...efer to unit wiring diagrams for thermostat or remote sensor connections GAS SUPPLY PIPING WARNING To prevent personal injury or death due to improper installation adjustment alteration service or mai...

Page 11: ...threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint unions 4 Install a drip leg to trap dirt and moisture before it can enter the gas valve The drip le...

Page 12: ...to convert units to propane gas NOx screens must be removed before converting to LP Remove burner assembly and pull NOx screens from each burner tube When all the screens are out reassemble the burner...

Page 13: ...supply gas pressure is less than 11 0 w c or greater than 13 0 w c 6 All pipe connections should be sealed with a pipe thread compound which is resistant to the fuel used with the furnace A soapy wat...

Page 14: ...Checks procedure provides a step by step sequence which if followed will assure the proper startup of the equipment in the minimum amount of time Air balancing of duct system is not considered part o...

Page 15: ...Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the terminal block TB1 Refer to Appendix A for blower performance at each speed tap Refer to Appendix D for maxi...

Page 16: ...16 Wiring Example...

Page 17: ...rmal manifold pressure for High fire is 3 5 w c on natural gas and 10 0 w c for propane gas Low fire natural gas 2 0 w c 6 0 w c low fire propane gas Minimum gas supply pressure is 5 0 w c for natural...

Page 18: ...Gas Only Check It is the responsibility of the contractor to adjust the gas input to the unit To measure the gas input use a gas meter and proceed as follows 1 Turn off gas supply to all other applian...

Page 19: ...speed will lower the temperature rise A slower blower speed will increase the temperature rise NOTE Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the...

Page 20: ...prior to resetting this manual reset control WARNING To avoid property damage personal injury or death due to fire or explosion a qualified servicer must investigate the reason for the rollout protec...

Page 21: ...the compressor control circuits will be ready to respond to a subsequent call for cooling Refrigeration Performance Check Check that compressor RLA corresponds to values shown in Appendix B RLA draw c...

Page 22: ...remove the filter access panel on return side of the unit Cabinet Finish Maintenance Use a fine grade automotive wax on the cabinet finish to maintain the finish s original high luster This is especi...

Page 23: ...dicates an internal fault check power supply to unit for proper voltage check all fuses circuit breakers and wiring Disconnect electric power for five seconds If LED remains off after restoring power...

Page 24: ...ce 4 FLASH CODE If the primary limit switch opens the gas valve is immediately deenergized the induced draft and air circulating blowers are energized The induced draft and air circulator blowers rema...

Page 25: ...62 859 0 62 0 2 1901 912 0 66 0 4 1787 909 0 66 0 4 1824 966 0 70 0 6 1702 955 0 69 0 6 1737 1014 0 73 0 8 1625 1005 0 73 0 8 1658 1067 0 77 0 2 2132 954 0 91 0 2 2175 1014 0 97 0 4 2056 993 0 95 0 4...

Page 26: ...4 70 0 70 0 7 2 6 5 50 6 49 9 70 0 70 0 Power Supply Model Number Electrical Rating Compressor Outdoor Fan Motor Indoor Fan Motor Optional Electric Heat Optional Powered Convienience Outlet FLA Optio...

Page 27: ...CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal...

Page 28: ...28 APPENDIX D MIN MAX AIRFLOW UNIT HEAT RANGE HIGH FIRE RATE BTU HR HEATING MINIMUM SCFM COOLING MINIMUM SCFM MAXIMUM SCFM GPG1660140M41 HIGH 140 000 1615 1500 2500 AIR FLOW RANGE FOR HIGH STAGE...

Page 29: ...RD YL YL BL VMC A1 A2 LS RD RD BK BK YL YL BK BK PU PU BK BK RS BK BK BK BK LPS ALS GAS PLM GAS PLF GR GY PU PU BL BR TN PU PU PU BL BR TN VM L1 L2 T1 T2 VMC F3 F3 FB3 4 BK RD PK BL BR GR YL WH PU GR...

Page 30: ...30...

Page 31: ...31...

Page 32: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Reviews: