All controls are shipped with the output voltage set to the industry standard 24VAC. To use the GL-
235 with older 12VAC valves, move jumper J4, located on the right side of the circuit board.
The GL-235 provides two different types of connections to the pool/spa actuators. For older
actuators with no wire end connector, a 3 position terminal block is used. Connect the wires to the
proper terminal block according to the color code shown in Figure 4. If the valve operates opposite
to the way it is supposed to, reverse the red and white wires. Be careful not to short the valve output
wiring. The GL-235 is fused and shorting the output will require replacing the fuse.
For newer Goldline, Compool, Hayward, and Jandy actuators (with wire end connectors), two 3-pin
connectors are supplied. Plug the actuator into one of the two 3 pin connectors as shown in figures
2 or 3. If the valve operates opposite to the way it is supposed to, disconnect and plug into the other
connector.
High Voltage (HV) output: Booster Pump
(model GL-235-LV-HV only)
The GL-235 can control a high voltage booster pump in addition to the normal low voltage solar
valve. Note the high voltage relay contacts are isolated so that the booster pump can be run on a
separate circuit, as required by many local codes. The GL-235 turns on, the valve output will operate
first, and then the HV relay will operate 30 seconds later.
High Voltage (HV) output: Timeclock Override
(model GL-235-LV-HV only)
The GL-235 can also be used to override the filter pump timer. This is very important if recirculate
freeze protection or nocturnal cooling functions are being used. Also, this function can be used on
systems where the system should operate whenever solar heat is available, regardless of the timer
settings. The HV relay will operate approximately 30 seconds after the LV relay.
Sensor Mounting and Wiring
Most installations use a PC sensor to measure the pool temperature and another PC sensor to measure
the solar temperature. Alternatively, an SC-¼ sensor can be screwed into the pump strainer basket
to measure the pool temperature.
Pool Sensor:
Drill a 3/8” (or 5/16”) hole in the PVC pipe. Remove burrs around the hole. Check
that the O-ring is seated on the PC sensor and then insert sensor into pipe. Tighten hose clamp over
the sensor to make a seal—DO NOT OVERTIGHTEN.
Solar Sensor:
Use a screw or silicon adhesive to attach the sensor near the solar collector array.
The sensor does not have to be attached to the collectors. It is only important that the sensor be
exposed to the same sunlight as the collectors. Additionally, the underside of the sensing element
may be covered with silicon to minimize wind cooling.
Other 10K ohm Goldline sensors may be substituted. Wire should be twisted pair 20AWG. Sensor
wiring run outdoors must be rated for outdoor use and ensure that the wire connections are
protected from the weather.
Do NOT run sensor wires in the same conduit or multiconduc-
tor cable as the valve actuator wires or any 120/240V circuit.
For long runs or runs near
other electrical wiring use shielded cable (Belden 8428 for outdoor use). Ground the shields to the
GL-35/LV ground screw.
240 VAC
input power
115 VAC
input power
EARTH
GROUND
EARTH
GROUND
{
{
LV-HV
ONLY
LV-HV
ONLY
Figure 1
3
Summary of Contents for GL-235-LV
Page 9: ...BasicInstallationofGL 235 LV Figure2 7...
Page 10: ...GL 235 LV HVwithHighVoltageOutputusedforTimerOverride Figure3 8...
Page 11: ...GL 235 LV HVwithHighVoltageOutputusedforBoosterPump Figure4 9...
Page 12: ...10 Measuring Voltage of Pool Sensor Use the same method to measure the Solar Sensor Figure5...