Freeze Protection

If you are relying on the collectors naturally draining to provide freeze protection, it is very important
that you use a 

non-positive seal valve or drill a hole (1/8"--1/4") in the diverter of a positive

seal valve to allow the collectors to drain.

  Alternatively, the GL-235 control can provide

recirculate freeze protection.  If enabled, when the GL-235 senses a freeze condition at the collector
sensor, it will allow circulation of relatively warm water from the pool to the collector panels.

The GL-235 will allow recirculation when the collector temperature falls below 40ºF and will stop
circulation when the collector temperature rises above 42ºF.  While this type of freeze protection
has proven to be adequate in relatively mild climates, it is extremely important that the sensors be
properly placed and that the homeowner realize that the system is unprotected in the event of a power
failure.  Recirculate freeze protection is NOT recommended in climates where freezing temperatures
are common or last for extended periods.

Goldline strongly recommends the use of GC-1 or GC-2 freeze snap switches if freeze protection is
being utilized.  Snap switches should be wired in series with the collector sensor.  Placement of the
snap switches at the coldest point of the collector array and exposed plumbing will help assure that
freeze protection starts early enough to protect the system.

The GL-235 is shipped from the factory with recirculate freeze protection disabled (the jumper is
present but installed on one pin only).  To activate recirculate freeze protection, install the jumper
across both pins marked “RECIRC”, located near the top right of the main circuit board.

If recirculate freeze protection is to be used on a GL-235, either:

     

The filter pump must be set for continuous operation

or

     

The GL235-LV-HV High Voltage Output must be wired for Timer Override function.

Nocturnal Cooling

The GL-235 has nocturnal cooling logic, which can be enabled/disabled via a jumper on the main circuit
board.  During nighttime hours, when enabled, the GL-235 will circulate relatively warmer water from
the pool to the collector panels, thus cooling the pool over time.  The GL-235 will circulate water
when the collector temperature AND the pool temperature is hotter than the high limit setting.
Circulation will stop when the collector temperature is 3ºF less than the pool temperature OR the
pool temperature is cooler than the high limit setting.  The GL-235 is shipped from the factory with
nocturnal cooling disabled (the jumper is present but installed on one pin only).  To activate nocturnal
cooling, install the jumper provided onto the two pins marked “COOLING” located near the top
right of the main circuit board.

If nocturnal cooling is to be used, either:

     

The filter pump must be set for continuous operation

or

     

The GL-235-LV-HV High Voltage Output must be wired for Timer Override function.

4

Summary of Contents for GL-235-LV

Page 1: ...3NF of the pool tem perature or the pool temperature is lowered below the set desired temperature SINGLE SETTING FOR DESIRED TEMPERATURE The GL 235 logic is set by a single dial adjustment with the d...

Page 2: ...eplacement SEE WARRANTY STATEMENT FOR COMPLETE DETAILS Service You Can Count On Visit www goldlinecontrols com or call 800 343 0826 to speak with a qualified technical support representative Our techn...

Page 3: ...GL 235 Solar Pool Controller Installation OperationManual for models GL 235 LV GL 235 LV HV www goldlinecontrols com 888 921 7665 North Kingstown RI USA LDLINE CONTROLS INC G...

Page 4: ...s spas and hot tubs These models provide differential temperature control with an adjustable calibrated water temperature high limit Automatic nocturnal cooling for pools that overheat in hot climates...

Page 5: ...ery important if recirculate freeze protection or nocturnal cooling functions are being used Also this function can be used on systems where the system should operate whenever solar heat is available...

Page 6: ...protection starts early enough to protect the system The GL 235 is shipped from the factory with recirculate freeze protection disabled the jumper is present but installed on one pin only To activate...

Page 7: ...n the MANUAL OFF position during cold weather Also note that the switch does NOT turn power off to the GL 235 Troubleshooting No Power Indicator Check main power circuit breakers Check fuse Fuse Repla...

Page 8: ...SENSOR indicator blinking If the CHECK SENSOR indicator is blinking there may be a possible open circuit or short circuit with the solar sensor Using a voltmeter measure the voltage across the termina...

Page 9: ...BasicInstallationofGL 235 LV Figure2 7...

Page 10: ...GL 235 LV HVwithHighVoltageOutputusedforTimerOverride Figure3 8...

Page 11: ...GL 235 LV HVwithHighVoltageOutputusedforBoosterPump Figure4 9...

Page 12: ...10 Measuring Voltage of Pool Sensor Use the same method to measure the Solar Sensor Figure5...

Page 13: ...29 51 19 377 3 30 91 7 164 2 09 131 2 987 1 15 12 58 774 4 27 52 18 870 3 27 92 6 999 2 06 132 2 926 1 13 13 57 014 4 25 53 18 377 3 24 93 6 839 2 03 133 2 867 1 11 14 55 313 4 23 54 17 899 3 21 94 6...

Page 14: ...warrants its solar control products installed outside of the USA or Canada to be free from defects in material or workmanship under normal use and service for one year from date of the initial system...

Reviews: