“CHECK SENSOR” indicator on

If the “CHECK SENSOR indicator is on and NOT blinking, there may be a possible open circuit or
short circuit with the pool sensor.  Using a voltmeter, measure the DC voltage across the terminals
of the pool sensor as indicated in figure 5.  If the voltage is close to zero volts, the sensor has a short
to ground.  Remove the sensor from the terminal block and measure the voltage across the pool
terminals again.  If the voltage is still close to zero volts, there is an internal short and the unit must
be returned for repair.  If the voltage is close to five volts, the pool sensor itself may be at fault.

With the sensor disconnected from the unit, measure the resistance of the sensor using an ohmmeter.
At room temperature (25ºC/77ºF) the sensor should measure approximately 10K  ohms (10,000
ohms ± 1%).  For other resistance measurements at different temperatures, consult the table at back
of manual.  If the sensor is not returning the correct value, it is defective and will need to be replaced.
If the sensor is returning approximately the correct value, reconnect it to the terminals marked
“POOL SENSOR”.  If the “CHECK SENSOR” indicator remains on, the unit is defective and needs
to be replaced.

“CHECK SENSOR” indicator blinking

If the “CHECK SENSOR indicator is blinking, there may be a possible open circuit or short circuit
with the solar sensor.  Using a voltmeter, measure the voltage across the terminals of the solar sensor.
If the voltage is close to zero volts, the sensor has a short to ground.  Remove the sensor from the
terminal block and measure the voltage across the solar  terminals again.  If the voltage is still close
to zero volts, there is an internal short and the unit must be returned for repair.  If the voltage is
close to five volts, the solar sensor itself may be at fault.

With the sensor disconnected from the unit, measure the resistance of the sensor using an ohmmeter.
At room temperature (25ºC/77ºF) the sensor should measure approximately 10K  ohms (10,000
ohms ± 1%).  For other resistance measurements at different temperatures, consult the table at back
of manual.  If the sensor is not returning the correct value, it is defective and will need to be replaced.
If the sensor is returning approximately the correct value, reconnect it to the terminals marked
“SOLAR SENSOR”.  If the “CHECK SENSOR” indicator remains on, the unit is defective and needs
to be replaced.

If FREEZE PROTECTION is enabled:

When a sensor is disconnected from the unit and freeze protection has been enabled, the SENSOR
FAULT light will NOT activate.  The GL-235 will recognize this as a freeze condition and activate
freeze protection.

6

Summary of Contents for GL-235-LV

Page 1: ...3NF of the pool tem perature or the pool temperature is lowered below the set desired temperature SINGLE SETTING FOR DESIRED TEMPERATURE The GL 235 logic is set by a single dial adjustment with the d...

Page 2: ...eplacement SEE WARRANTY STATEMENT FOR COMPLETE DETAILS Service You Can Count On Visit www goldlinecontrols com or call 800 343 0826 to speak with a qualified technical support representative Our techn...

Page 3: ...GL 235 Solar Pool Controller Installation OperationManual for models GL 235 LV GL 235 LV HV www goldlinecontrols com 888 921 7665 North Kingstown RI USA LDLINE CONTROLS INC G...

Page 4: ...s spas and hot tubs These models provide differential temperature control with an adjustable calibrated water temperature high limit Automatic nocturnal cooling for pools that overheat in hot climates...

Page 5: ...ery important if recirculate freeze protection or nocturnal cooling functions are being used Also this function can be used on systems where the system should operate whenever solar heat is available...

Page 6: ...protection starts early enough to protect the system The GL 235 is shipped from the factory with recirculate freeze protection disabled the jumper is present but installed on one pin only To activate...

Page 7: ...n the MANUAL OFF position during cold weather Also note that the switch does NOT turn power off to the GL 235 Troubleshooting No Power Indicator Check main power circuit breakers Check fuse Fuse Repla...

Page 8: ...SENSOR indicator blinking If the CHECK SENSOR indicator is blinking there may be a possible open circuit or short circuit with the solar sensor Using a voltmeter measure the voltage across the termina...

Page 9: ...BasicInstallationofGL 235 LV Figure2 7...

Page 10: ...GL 235 LV HVwithHighVoltageOutputusedforTimerOverride Figure3 8...

Page 11: ...GL 235 LV HVwithHighVoltageOutputusedforBoosterPump Figure4 9...

Page 12: ...10 Measuring Voltage of Pool Sensor Use the same method to measure the Solar Sensor Figure5...

Page 13: ...29 51 19 377 3 30 91 7 164 2 09 131 2 987 1 15 12 58 774 4 27 52 18 870 3 27 92 6 999 2 06 132 2 926 1 13 13 57 014 4 25 53 18 377 3 24 93 6 839 2 03 133 2 867 1 11 14 55 313 4 23 54 17 899 3 21 94 6...

Page 14: ...warrants its solar control products installed outside of the USA or Canada to be free from defects in material or workmanship under normal use and service for one year from date of the initial system...

Reviews: