Limitid indikator GWG - type GWS -issue 1
2 / 12
part no. 15 382 64 c
SUITABLE TANKS
The limit indicator may only be installed and used in the following overground and
underground tanks which are constructed indoors and outdoors:
Table1:
Type GWS limit indicator for tanks
Tanks
pursuant to standard
above-ground battery tanks
DIN 6620
above-ground cylindrical, horizontal steel
tanks
DIN 6616, DIN 6617, DIN 6624-1, DIN 6624-2,
ÖNORM C 2115,
ÖNORM C 2118, EN 12285-2,
underground cylindrical, horizontal steel
tanks
DIN 6608-1, DIN 6608-2, EN 12285-1,
ÖNORM C 2110
locally manufactured tanks made of steel
for above-ground storage
DIN 6625-1, DIN 6625-2, ÖNORM C 2117
cylindrical, vertical steel tanks
DIN 6618-1, DIN 6618-2,
DIN 6618-3, DIN 6619-1, DIN 6619-2,
DIN 6623-1, DIN 6623-2,
ÖNORM C 2116
Tanks
NBN I 03-002, NBN I 03-003, NBN I 03-004
above-ground cylindrical flat-bottom tank
structures made of metal materials
DIN 4119-1, EN 1993-4-2, EN 14015
stationary pressure-free tanks made of
thermoplastics
EN 13341, EN 13575
above-ground GRP tanks
EN 13121 parts 1 to 4
other tanks
including certificate of suitability for intended
use issued by the building inspectorate
The certificates of suitability for intended use of the tanks, e.g. regarding admissible
operating media, must be observed.
Further fields of application
•
Fuel oil tanks in the meaning of RheinSCHUO “Rhine Vessel Inspection Regulation".
•
Fuel tanks for vessels in the meaning of the worksheet DWA-A 783 “Fuelling stations for
vessels“.
•
Limit indicator in fuel reservoirs of vehicles.
FUNCTION DESCRIPTION
Type GWS limit indicator GWG
In accordance with the regulations for protecting waterways against pollution, overfilling of
tanks used to store liquid fuels must be prevented. This basic requirement is met if road
tankers are equipped with an overfill prevention mechanism (EN 13616: Steuereinrichtung am
Straßentankfahrzeug) automatically preventing the tanks from being overfilled in cooperation
with a limit indicator specified according to worksheet DWA-A 779, DWA-A 791-1, DIN 4755
and VdTÜV leaflet Tank systems 964, respectively.
The GWG series limit indicators meet the requirement according to harmonised
EN 13616 as sensors for tanks with current interface as part of a type B1 overfill protection
device and meet the withdrawn TrbF 511 regarding their design. GOK limit indicators meet
the demands on the condition of both EN 13616 and TrbF 511.