Limit indikator GWG type GWD
8 / 12
Part no. 15 382 56 b
Table 6:
Calculation option for the adjusting dimension X
a = dimension a= H - L
1
- b
b = tank wall thickness
H = height or diameter of the tank
k = height bushing or threaded flange
1. maximum volumetric flow rate of the booster pump of the road tanker
Q
max
L/min
2. switching and closing delays of the booster pump of the road tanker
Time
Level sensor according to measurement / datasheet
t
1
s
Switch / relay / or such like
t
2
s
Booster pump, flow time
t
3
s
Shut-off fitting:
•
mechanical, manually operated time alarm to closing start, closing
time:
•
electrically, pneumatically, or hydraulically operated, closing time:
t
4
s
s
Total time (t
total
=
t
1
+ t
2
+ t
3
+ t
4
):
T
total
s
3. Overrun volume
V
4
Overrun volume from delays:
V
1
=
Q
max
• (
t
total
/ 60)
V
1
L
Overrun volume from filler line:
V
2
= (
π
/ 4) •
D
i
² •
L
FL
/ 1000
D
i
= internal pipe diameter in mm
L
FL
= length of the filler line in m
V
2
L
V
4
=
V
1
+
V
2
V
4
L
4. Level
L
1
Volume at admissible level according to table 1 issue 1.
V
3
L
Overrun volume
V
4
L
Volume at level
L
1
V
5
=
V
3
-
V
4
V
5
L
Then, the volume at level
V
5
value results, in combination with the calibration chart or by
calculation, in the level
L
1
.
The adjusting dimension
X
for the GWG must be determined taking into account* the tank
shape:
Installation on tank ceiling:
X = H - L
1
- b
=
mm
*
if applicable Take into account ADJUSTING DIMENSION
X
AND SUBSEQUENT LEAK
PROTECTION LINING.
Summary of Contents for GWD
Page 10: ...Grenzwertgeber Baureihe GWG Typ GWD Heft 1 10 12 Artikel Nr 15 382 70 e ...
Page 11: ...Grenzwertgeber Baureihe GWG Typ GWD Heft 1 Artikel Nr 15 382 70 e 11 12 ...
Page 22: ...Limit indikator GWG type GWD 10 12 Part no 15 382 56 b ...
Page 23: ...Limit indikator GWG type GWD Part no 15 382 56 b 11 12 ...
Page 35: ...Limiteur de remplissage GWG type GWD carnet 1 Référence 15 382 76 b 11 12 ...
Page 46: ...Grenswaardesensor GWG type GWD Schrift 1 10 12 Artikelnr 15 382 78 b ...
Page 59: ...Czujnik wartości granicznej GWG typ GWD zeszyt 1 Nr artykułu 15 382 58 e 11 12 ...
Page 70: ...Sensor de límite tipo GWD Cuaderno 1 10 12 N º de artículo 15 382 68 a ...
Page 71: ...Sensor de límite tipo GWD Cuaderno 1 N º de artículo 15 382 68 a 11 12 ...