Limit indikator GWG type GWD
6 / 12
Part no. 15 382 56 b
Filling and water control in Germany
According to § 23 "Requirements for filling and draining" of the Ordinance on Installations for
Handling Substances Hazardous to Water (AwSV), this applies to Germany:
“(1) The person filling or draining an installation shall be obliged to monitor this process and
to make sure, prior to starting any work, that the required safety equipment is in a proper
condition. The admissible exposure limits of the installations and safety equipment must be
adhered to when filling or draining.”
(2) Tanks in installations for handling liquid substances hazardous to water may only be filled
with fixed pipe connections using an overfill protection.
(3) Tanks in fuel storage installations may only be filled from road tankers, demountable tanks
and portable tanks using an automatically closing filling safety device. Fuel oil consumer
systems with a volume of up to 1.25 m
3
may also be filled using self-closing nozzles,
notwithstanding sentence 1."
ADJUSTING DIMENSION X
The tables of the manual issue 2 regarding the adjusting dimension
X
are based on a level
L
1
for the length of the filler line
to 20m
. Level
L
1
is the reference dimension for
X
.
If, for storing, filling, and handling water-hazardous substances, the filler line on the
installation is
longer than 20m
, the level
L
1
must be reduced:
Criterion:
•
Overrun volume in the filler line
•
the adjusting dimension
X
must be re-determined according to the special conditions
•
the admissible level with
L
max
of tanks according to table 5 must not be exceeded, e.g. level
indicator maximum on the tank and on the level gauge, respectively
Table 5:
Admissible level at L
max
of tanks for fuels
Admissible
level
6)
Tank
Fuel oil
Fuel
Depth
Above-ground Underground
5)
90% (
V/V
)
7)
X
X
X
---
95% (
V/V
)
X
X
X
---
X
X
X
< 0.3m
1) 2) 4)
X
X
X
< 0.8m
3) 10)
X
X
X
ns
8)
97% (
V/V
)
X
X
X
≥ 0.3m
1) 2) 4)
X
X
X
≥ 0.8m
3) 10)
X
X
≥ 1,0 m
11)
98% (
V/V
)
X
X
X
9)
3)
Acc. DIN 4755
1)
Only for fuels with a spatial thermal
expansion coefficient ß ≤ 85 • 10
-5
/K, e.g. fuel oil EL
2)
Only for fuels with a spatial thermal expansion coefficient ß ≤ 85 • 10
-5
/K, e.g. diesel fuel
4)
Acc. to TRÖl edition 2.
1
and DWA-A 791 (TRwS)
3)
Type GWS only
6)
Maximum admissible storage volume < actual tank volume
7)
Tanks in rail vehicles according to EN 45545-7
11)
Acc. TRBS 3151 / TRGS 751
8)
Applicable in Austria for tanks, pursuant to TRÖL 3rd edition
9)
Applicable in Belgium
10)
Acc. to VdTÜV leaflet Tank systems 967
Summary of Contents for GWD
Page 10: ...Grenzwertgeber Baureihe GWG Typ GWD Heft 1 10 12 Artikel Nr 15 382 70 e ...
Page 11: ...Grenzwertgeber Baureihe GWG Typ GWD Heft 1 Artikel Nr 15 382 70 e 11 12 ...
Page 22: ...Limit indikator GWG type GWD 10 12 Part no 15 382 56 b ...
Page 23: ...Limit indikator GWG type GWD Part no 15 382 56 b 11 12 ...
Page 35: ...Limiteur de remplissage GWG type GWD carnet 1 Référence 15 382 76 b 11 12 ...
Page 46: ...Grenswaardesensor GWG type GWD Schrift 1 10 12 Artikelnr 15 382 78 b ...
Page 59: ...Czujnik wartości granicznej GWG typ GWD zeszyt 1 Nr artykułu 15 382 58 e 11 12 ...
Page 70: ...Sensor de límite tipo GWD Cuaderno 1 10 12 N º de artículo 15 382 68 a ...
Page 71: ...Sensor de límite tipo GWD Cuaderno 1 N º de artículo 15 382 68 a 11 12 ...