10.7 Documentation
After pressing the [OK] button, the display changes to the „Test result“
screen (Fig. 37).
Here you can see all the measurement results with the related limit values.
If the measurement results of the electrical values, the visual inspection and
the function test were all in order, the following message appears:
“Test OK“.
If the test was not successful the message says:
“Test not OK!“.
At this point you can cancel the test with the [cancel] button (the display
goes back to the „Settings for measuring“ screen) or switch to the „Memory
menu“ with the [next] button.
In the „Memory menu“ (Fig. 38) you can confirm or modify the following
parameters: device ID number, device designation, name of the inspector,
date and customer number.
You can also change the storage location – from internal memory to MMC/
SD card and vice-versa.
The current setting is displayed via a symbol in the headline of the memory
menu.
The appliance identification can also be read from a barcode label
using the optional barcode scanner.
To do this, before starting up the appliance tester connect the plug
of the barcode scanner to the RS232 socket of the tester and
screw it tight.
Fig. 37
Fig. 38
Fig. 39
29
Operating manual for the TG uni 1, TG euro 1 and TG euro 1 med appliance tester
Conducting tests in accordance with DIN VDE 0701-0702, Example 1 – Devices with a protective conductor (PC I)
f
f
f
Symbols for memory settings:
– Internal memory
– MMC/SD memory card