Glow-worm ULTIMATE 30c Installation And Servicing Manual Download Page 7

0020167175_01 - 02/13 - Glow-worm

3  Safety instructions and regulations

3.1 Safety 

instructions

If the gas pressure at the input of the appliance is outside the 

range speci

fi

 ed, the appliance must not be put into operation.

e

 DANGER: 

Incorrect installation can cause electric shock or 

appliance damage.

• 

Never disable security devices and do not try to adjust them.

With regards to the “Manual Handling Operations, 1992 

Regulations”, the appliance exceeds the recommended weight for 

a one person lift.

The handling of the boiler may involve lifting, pushing and 

pulling, the use of a sack truck may be required.

• 

Be sure to consider the following handling techniques and 

precautions:

 - Grip the appliance at its base

 - Use safety clothing where appropriate, e.g. gloves, safety 

footwear.

• 

Ensure safe lifting techniques are used:

 - Keep back straight.

 - Avoid twisting at the waist.

 - Avoid upper body/top heavy bending.

 - Always grip using the palm of the hand.

 - Use designated hand holds.

 - Keep load as close to body as possible.

 - Always use assistance if required.

• 

Under no circumstances must the user interfere with or adjust 

sealed parts.

• 

When assembling the connections, correctly position the seals 

to avoid any leakage of gas or water.

• 

This appliance contains metal parts (components) and care 

should be taken when handling and cleaning, with particular 

regard to edges.

The basic safety instructions must be followed before attempting 

to maintain or replace spare parts:

• 

Stop the appliance.

• 

Electrically isolate the appliance from the power supply.

• 

Turn o

  the appliance gas isolation valve.

• 

Hydraulically isolate the appliance using the isolation valves if 

provided.

• 

Should you need to replace hydraulic components, drain the 

appliance.

• 

Protect all the electrical components from water while working 

on the appliance.

• 

Use only original spare parts.

• 

Use only new O-rings and gaskets.

• 

After having completed work on gas or water carrying 

components, check for their tightness.

• 

When work on the appliance is completed, perform an 

operational test and check for safety.

3.2 Regulations 

3.2.1 Statutory 

requirements

IMPORTANT

Where no British Standards exists, materials and equipment 

should be 

fi

 t for their purpose and of suitable quality and 

workmanship.

The installation of this boiler must be carried out by a competent 

person approved at the time by the Health and Safety Executive 

and in accordance with the rules in force in the countries of 

destination.

Manufacturer’s instructions must not be taken as overriding 

statutory requirements.

Statutory Requirements

In GB, the installation of the boiler must comply with the 

requirements of the current issue of BS6798 and be carried out 

by a competent person approved at the time by the Health and 

Safety Executive and as described in the following regulations:

- The manufacturer’s instructions supplied.

- The Gas Safety (Installation and Use) Regulations.

- The appropriate Buildings Regulations either The Building 

Regulations, The Building Regulations (Scotland), The Building 

Regulations (Northern Ireland).

- The Water Supply (water 

fi

 ttings) Regulations 1999 and water 

byelaws 2000, Scotland.

- The Health and Safety at Work Act, Control of Substances 

Hazardous to Health (COSHH).

- Any electrical work must conform to BS7671 and part P of the 

building regulations where applicable.

Where no speci

fi

 c instructions are given, reference should be 

made to the relevant British Standard Code of Practice.

In IE, the installation must be carried out by a competent person 

approved at the time by the Health and Safety Executive and 

installed in accordance with the current edition of I.S.813 

“Domestic Gas Installations”, the current Building Regulations 

and reference should be made to the current ETCI rules for 

Electrical Installation.

GB: the following Codes of Practice apply: BS4814, BS6798, 

BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, 

BS7074 Part 1 and 2, BS7593, BS7671.

IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.

NOTE: For further information, see the current issue of the 

Building Regulations, approved document L1 ( in the UK) and the 

following current issues of:

1) Central heating system speci

fi

 cation (CheSS) and

2) Controls for domestic central heating system and hot water. 

BRECSU.

INTRODUCTION

- 5 -

Summary of Contents for ULTIMATE 30c

Page 1: ...condens Installation and Servicing ULTIMATE 30c G C No 47 044 48 ULTIMATE 35c G C No 47 044 49...

Page 2: ......

Page 3: ...Appliance location 8 6 1 Location 8 6 2 Clearances 8 6 3 Ventilation 8 7 Appliance installation 9 7 1 Scope of delivery 9 7 2 Recommendations before installing 9 7 3 Dimensions 10 7 4 Mounting 11 8 Hy...

Page 4: ...shooting 28 14 1 Fault diagnosis 28 14 2 Fault memory 29 14 3 Fault codes 29 14 4 Functional flow diagram 31 15 Gas conversion adjustments 32 15 1 Settings 32 15 2 Restart re check commissioning 33 1...

Page 5: ...g safety The appliance is designed to recognise the potential for an overheat lockout and will shutdown before this happens 2 1 2 Safety discharge valve A safety discharge valve and discharge pipe are...

Page 6: ...ent person approved at the time by the Health and Safety Executive and that it meets the requirements of the appropriate Building Regulations The Benchmark Checklist can be used to demonstrate complia...

Page 7: ...onal test and check for safety 3 2 Regulations 3 2 1 Statutory requirements IMPORTANT Where no British Standards exists materials and equipment should be fit for their purpose and of suitable quality...

Page 8: ...of the boiler including any heating controls to the electrical supply MUST be through one common isolator and must be fused 3 Amp maximum 3 2 2 Other regulations Control of Substances Hazardous to Hea...

Page 9: ...trical power W 6 6 Operational mode electrical power Max W 151 151 Internal fuse rating on main PCB A 2 2 Index of electrical protection EN 60529 IPX4D IPX4D Description Unit 30 35 Gas connection O D...

Page 10: ...building it should be fitted in accordance with the Institute of Gas Engineers document IGE UP 7 1998 If in doubt seek advice from local gas undertaking or Glow worm 6 2 Clearances To allow periodic...

Page 11: ...estic flow is 1 0 bar The maximum working pressure of the domestic hot water circuit is 10 bar If the cold water supply pressure exceeds this then a pressure reducing valve must be fitted in the suppl...

Page 12: ...ng systems are shown diagrammatically see diagram below 3 2 1 4 7 6 5 Key 1 Heating flow circuit 2 Heating return circuit 3 Boiler 4 Double check valve assembly 5 Domestic cold water supply in 6 Tempo...

Page 13: ...ue 80 125 flue 130mm Use a 125mm diameter core drill for internal access only flue installation 60 100 flue 80 125 flue 150mm i IMPORTANT If flue extension pipes are to be used then a core drill size...

Page 14: ...s operation Do not use any solvent products due to the risk of damaging the circuit a DANGER Do not perform any hot work directly under the appliance this may cause damage to the appliance base Heat m...

Page 15: ...e pipe 2 Condensate outlet pushfit Make sure there is no protective plug fitted Connect the condensate pipe 1 to the condensate outlet 2 i IMPORTANT The pipe should have a fall of a least 2 5 44mm met...

Page 16: ...0020167175_01 02 13 Glow worm INCREASE PIPE SIZE 75 mm min 100 mm min Washing machine trap waste 44 2 5 INSTALLATION 14...

Page 17: ...Being a condensing boiler some pluming may occur from the flue outlet This should be taken into consideration when selecting the position for the terminal Carports or similar extensions of a roof onl...

Page 18: ...onal 90 bend is necessary or 2 at 45 the length L must be reduced by 1 m When using the Plume Management Kit the maximum lengths flue pipe A and B 60 100mm are A m 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5...

Page 19: ...C 60 C 72 9 73 1 10 Electrical connections e DANGER Incorrect installation can cause electric shock or appliance damage The electrical connection of the appliance must be made only by a qualified engi...

Page 20: ...850C insulated cable not less than 0 75mm 24 0 20 A fused three pin plug and shuttered socket outlet may be used instead of a fused spur box provided that it is not used in a room containing a fixed...

Page 21: ...s as below Resistance to earth 1 Ohm Short circuit test L N Resistance to earth L E Polarity check 10 3 2 230V permanent supply 230V system controls a DANGER All cables connected to the appliance shou...

Page 22: ...4 13 5 14 6 15 7 16 8 17 9 18 X20 1 2 3 4 1 1 2 1 X21 Green Yellow Green Yellow 18 17 16 1 2 3 4 9 6 5 8 7 10 11 12 13 14 15 Key 1 Control accessories connector 2 Reserved for future use 3 Location fo...

Page 23: ...he gas supply Switch on the power supply to the appliance Make sure that the domestic hot water and heating functions on your appliance are not activated 11 3 Filling the CH system Central heating Mak...

Page 24: ...been installed in accordance with the instructions Check the integrity of the flue system and flue seals Check the integrity of the appliance combustion circuit and relevant seals Check that all inte...

Page 25: ...top watch at least 10 minutes after the burner has lit see table below for approximate rates Gas rates G20 Gas rates G31 approx after 10 mins from cold Model MIN MAX MIN MAX m3 h ft3 h m3 h ft3 h kg h...

Page 26: ...the user IE it is necessary to complete a Declaration of Conformity to indicate compliance to I S 813 An example of this is given in the current edition of I S 813 12 Specified Adjustment 12 1 Heating...

Page 27: ...ure measured by the external sensor no d 67 Time remaining before the end of the anti cycle in heating mode min Display the time remaining before the end of the anti cycle no d 71 Maximum temperature...

Page 28: ...ivated 1 activated 0 yes 12 4 Status of the appliance Press button for more than 3 seconds to learn the current state of functioning of the appliance The screen displays S and the state of the applian...

Page 29: ...installed check the operation of the appliance Start the appliance to ensure that any adjustments operate correctly and check that the appliance operates safely Check the gas tightness and water tigh...

Page 30: ...Make sure that the electricity supply has not been interrupted and that the appliance is connected correctly See chapter Trouble shooting Fault diagnosis Check the electrical installation Check the ap...

Page 31: ...ssure of the installation 0 3 bar Return water valve closed Pump disconnected Leak in the installation Fill the installation Purge the installation Check the pump connections Check the flow and return...

Page 32: ...nce Check temperature sensors connections Replace faulty sensors F73 Heating circuit pressure sensor fault The sensor is shorted or disconnected Check the sensor s connections Check the sensor F74 Hea...

Page 33: ...0020167175_01 02 13 Glow worm 14 4 Functional flow diagram 14 4 1 Central Heating 14 4 2 Domestic Hot Water MAINTENANCE 31...

Page 34: ...converted See chapter Commissioning Tools required to make the conversion are a 4mm Allen key and an electricians screwdriver Having checked the appliance and system have been installed in accordance...

Page 35: ...eating circuit of the boiler only by closing the heating flow and return isolating valves See chapter Hydraulic connection Gas and water connections Open the drain point 2 Attach a length of hose 1 if...

Page 36: ...eck that the pressure sensor is working properly The pressure must be displayed on the screen Check the pressure of the expansion vessel 17 1 2 Other checks Check the CO2 rate in the fuel and compare...

Page 37: ...2 Preliminaries Prior to during servicing and after any maintenance or changed parts the following inspection must be carried out The integrity of the flue system and flue seals The integrity of the...

Page 38: ...to achieve the required results for either the combustion or gas rates it will be necessary to complete a full service of the appliance and then repeat the combustion check procedure If after servicin...

Page 39: ...Use protective gloves 5 3 2 4 1 6 Key 1 Condensate cleaning cap 2 Condensate pipe 3 Condensate outletv 4 Condensate retaining screw 5 Condensate trap 6 Hose Place a container under the condensate tra...

Page 40: ...t exchanger 12 Burner door seal 13 Burner 14 Gas valve 15 Fan 16 Fan connection 17 Gas pipe 17 8 1 Spark electrode Disconnect the electrode inlet 3 and the grounding cable 2 Remove the 2 spark electro...

Page 41: ...tion check On completion of the service the Benchmark Service Record sould be completed 18 Replacement of Parts Do not use reconditioned or copy parts only use original parts supplied by Glow worm If...

Page 42: ...5 Remove the steel washer 4 Remove fibre washer 1 Remove the glass 3 18 3 1 Expansion vessel B C D E A 3 2 1 4 2 1 Key 1 Connector 2 Expansion vessel 3 Upper support bracket 4 Retaining screw 5 Gaske...

Page 43: ...17 Automatic air vent 18 Expansion vessel pipe clip 19 Automatic air vent retaining clip 20 Pump head retaining screws 21 Pump housing 22 Pump head connector 23 Plate to plate heat exchanger retaining...

Page 44: ...urise the boiler 18 4 5 Flow sensor and impeller Remove the the electrical connection 12 Unclip the flow sensor 13 Unscrew the impeller housing 28 and remove the impeller 18 4 6 Bypass Drain the boile...

Page 45: ...ut 13 Combustion burner door assembly seal 14 Burner gasket 15 Burner 16 Burner retaining screw 17 Heat exchanger retaining screw 18 Heat exchanger retaining bracket 19 Burner gate retaining screw 20...

Page 46: ...t exchanger out Drain the boiler heating and hot water circuits as described in the appropriate chapter Draining Remove the flue connection Undo the two screws located on the top of each side panel Re...

Page 47: ...18 6 Condensate trap b ATTENTION Condensate is mildly acidic Wear protective gloves 5 3 2 4 1 6 Key 1 Condensate reservoir 2 Condensate discharge 3 Condensate outlet 4 Condensate retaining screw 5 Con...

Page 48: ...to the PCB When refitting the user interface ensure the leads are not trapped 18 7 4 Mains supply cable e DANGER The main supply cable must be replaced by a qualified and competent electrician If the...

Page 49: ...low and return 4 0020097279 Gas valve 5 0020038441 Electrode assembly 6 0020118159 User interface PCB Key No Part No Description GC Part No 7 0020136541 Plate to plate heat exchanger 30c 0020173017 Pl...

Page 50: ...olystyrene end packs Remove top polystyrene pack with fittings Positioning of Appliance for Final Installation no obstructions Recommend 2 persons lift appliance to position into place Fit bracket sec...

Page 51: ...Declaration of Conformity Installation Commissioning and Service Record...

Page 52: ...a...

Page 53: ...r ID Number Comments Signature SERVICE 7 Date EnerJ I ciency Checklist completed Yes No Engineer Name Company Name Telephone Number Engineer ID Number Comments Signature SERVICE 9 Date EnerJ I ciency...

Page 54: ......

Page 55: ......

Page 56: ...ing changes GLOW WORM Nottingham Road Belper Derbyshire DE56 1JT Because of our constant endeavour for improvement details may vary slightly from those shown in these instructions www glow worm co uk...

Reviews: