0020167175_01 - 02/13 - Glow-worm
9.2 Flue
con
fi
guration description
9.2.1 Horizontal
concentric
fl
ue Ø 60/100 mm
or Ø 80/125 mm (C13 type installation)
a
DANGER:
If necessary, you must install a terminal protection kit.
Ø 60/100 mm
L
63
1
Key
1 Gasket (
fi
tted)
Ø 80/125 mm
L
1
Key
1 Gasket (
fi
tted)
Type
Max length
Ø 60/100
6 m
Ø 80/125
10 m
Each time an additional 90° bend is necessary (or 2 at 45°), the
length (L) must be reduced by 1 m.
When using the Plume Management Kit, the maximum lengths
fl
ue pipe A and B (60/100mm) are:
A (m)
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5
B (m)
5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5
•
Refer to the Plume Management Kit installation manual.
9.2.2 Vertical
concentric
fl
ue Ø 60/100 mm
or Ø 80/125 mm (C33 type installation)
L
Type
Max length (L)
Ø 60/100
6 m
Ø 80/125
10 m
Each time an additional 90° bend is necessary (or 2 at 45°), the
length (L) must be reduced by 1 m.
INSTALLATION
- 16 -