14.2 Fault
memory
•
This menu allows you to display the 10 most recent failure
codes registered by the appliance.
•
In order to display the fault code memory, simultaneously
press the buttons and for more than 7 seconds.
•
The screen will display the
fi
rst fault "1." (record) and after
"XX" (fault code).
•
To display the other faults registered by the appliance, press
the button or .
•
Press button
for more than 3 seconds to exit this menu.
•
To erase the fault memory registered by the appliance, consult
the “Installation adjustments” chapter and use code “d.94”.
14.3 Fault
codes
i
IMPORTANT:
The faults described in this chapter should be carried
out by a quali
fi
ed engineer and if needed by the After
Sales Service.
Fault
codes Description
Cause
Solution
F00
Flow heating temperature sensor fault
Sensor open circuit
• Check the sensor’s connections.
• Check the wiring harness.
• Check the sensor.
F01
Return heating temperature sensor fault Return heating temperature sensor
disconnected
F10
Flow heating temperature sensor fault
Sensor short-circuit
F11
Return heating temperature sensor fault Return heating temperature sensor shorted.
F20
Overheating fault
Overheating safety device activated (97°C)
• Check the operation of the pump.
• Check the wiring harness.
• Check that the
fl
ow and return heating isolation
valves are open.
F22
Water pressure of the installation (<0.3
bar)
Return water valve closed
Pump disconnected
Leak in the installation
• Fill the installation.
• Purge the installation.
• Check the pump connections.
• Check the
fl
ow and return heating sensor
connections.
• Check that there are no leaks.
F23
Maximum temperature di
ff
erence
reached between return and
fl
ow
heating
Water circulation fault
• Check the
fl
ow and return heating sensor
connection.
• Check the pump speed.
F24
Water circulation fault
Malfunction of the pump (excessively rapid
temperature increase)
• Check that the
fl
ow and return heating isolation
valves are open.
F26
Fault in gas valve motor.
Disconnected or defective cables
• Check the gas valve connections.
• Check the operation of the gas valve.
• Check the operation of the condensate pump (option).
F27
Flame detection fault.
Abnormal
fl
ame detection
• Check the
fl
ame detection electrode.
• Check the main board.
• Check the igniter unit.
F28
Ignition fault
No return gas / Insu
ffi
cient gas
fl
ow
Gas valve incorrectly adjusted
Defective
fi
ring electrode and
fl
ame control /
Defective igniter unit
• Check the return gas circuit (gas valve open).
• Check the observe the
fl
ame picture and check the
CO
2
setting.
• Check the igniter unit connections.
• Check the state of the electrode (corrosion).
F29
Loss of
fl
ame during operation
F32
Incorrect air pressure
Incorrect fan speed.
• Check the entire
fl
ue system.
• Check the fan’s electrical connections.
F49
EBUS voltage fault
Fault in EBUS line
Short circuit in EBUS connector
• Check that the eBus controls are
fi
tted and wired
correctly.
MAINTENANCE
- 29 -