221473B
Diagram 3.5
3 Fault Finding
5065
Is fan turning.
Is there 230ac between
yellow on CH Overheat
Thermostat and Neutral.
Faulty CVI
ignition unit.
Faulty APS,
replace.
Is there 230ac on brown
and blue, on fan ?
Faulty CVI
ignition
unit, replace.
Faulty fan,
replace.
Is there 230ac between
brown pin 10 and blue
pin 11 an CVI ignition
connector ?
Is there 24V ac on white
and red CNI on main PCB ?
Faulty
transformer,
replace.
Faulty main
PCB, replace.
Is there between
15 - 30 V DC on the two
greys on CN1 main PCB ?
Is there between
15 - 30 V DC on the
Modureg coil ?
Faulty CVl
ignition unit.
Faulty coil.
Faulty main
PCB.
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO