System 3000
Blind timer and timer BT, Operating top unit BT
Parameters
Setting options,
Default setting
Explanations
Travelling time
1 ... 360 s
Default setting: 120 s
Absolute time which the blind/shutter requires
from the top to the bottom end position. The
entry is essential if position movements are to
occur.
Slat adjusting
time
0 ... 10 s
Default setting: 0 s
Absolute time for changing-over Venetian
blind slats. Here, the fabric-stretching time can
be set for the operation of awnings.
Inverse operation On, Off
Default setting: Off
Inverts the activation of the relay outputs. Dur-
ing inverted operation, the relay outputs "Up"
and "Down" should be activated in reverse.
This is required, for example, for controlling
skylights.
Blind/shutter
height ventilation
position
0 ... 100 %
Default setting: 100%
The blind/shutter stops in this position when
shutting down. This parameter is only visible in
the shutter operating mode.
Slat position
ventilation posi-
tion
0 ... 100 %
Default setting: 100%
Ventilation position in the "Venetian blind" op-
erating mode: The blind/shutter moves to the
lower end position and the slats tilt to the
value set here.
Settings with optional brightness temperature sensor
Parameters
Setting options,
Default setting
Explanations
Teach brightness
sensor
Input MAC address.
After entering the MAC address, the received
brightness for the controller is used by bright-
ness-dependent switching operations.
Brightness evalu-
ation
On, Off
Default setting: Off
If brightness evaluation is switched on and the
brightness threshold value is exceeded for
more than 2 minutes, sun protection is carried
out. If the brightness falls below the set bright-
ness threshold value for longer than 15
minutes, sun protection is deactivated.
Brightness
threshold
4,000 ... 80,000 lux
Default setting: 20,000 lux
Brightness threshold to carry out sun protec-
tion
Sun protection
action active
Depending on the insert
used
Switching, dimming or
moving the blind/shutter
The set value is called up when the brightness
threshold value is exceeded.
E.g. for Venetian blind inserts, the set sun pro-
tection position is approached.
Sun protection
action inactive
Depending on the insert
used
Switching, dimming or
moving the blind/shutter
The set value is called up when the brightness
threshold value is not reached.
E.g. the movement to the upper end position
(0 %) can be set for Venetian blind inserts.
Temperature
evaluation
On, Off
Default setting: Off
If temperature evaluation is activated, before
implementing the sun protection, the preset
temperature threshold is checked to see if it
was exceeded. If this is not the case, the sun
protection is implemented only when the tem-
perature exceeds.