HD50
- 36 -
V1.5
Address
Type
Holding Register description
1012 +
200 x (
N
-1)
SW
Lower alarm threshold for
TEMPERATURE
with
TC_K
sensor of channel
N
in
the set measurement unit (x10).
1013 +
200 x (
N
-1)
SW
Higher alarm threshold for temperature with TC_K sensor of channel N in
the set measurement unit (x10).
1014 +
200 x (
N
-1)
SW
Lower alarm threshold for
TEMPERATURE
with
TC_J
sensor of channel
N
in
the set measurement unit (x10).
1015 +
200 x (
N
-1)
SW
Higher alarm threshold for temperature with TC_J sensor of channel N in
the set measurement unit (x10).
1016 +
200 x (
N
-1)
SW
Lower alarm threshold for
TEMPERATURE
with
TC_T
sensor of channel
N
in
the set measurement unit (x10).
1017 +
200 x (
N
-1)
SW
Higher alarm threshold for temperature with TC_T sensor of channel N in
the set measurement unit (x10).
1018 +
200 x (
N
-1)
SW
Lower alarm threshold for
TEMPERATURE
with
TC_N
sensor of channel
N
in
the set measurement unit (x10).
1019 +
200 x (
N
-1)
SW
Higher alarm threshold for temperature with TC_N sensor of channel N in
the set measurement unit (x10).
1026 +
200 x (
N
-1)
SW
Lower alarm threshold for
TEMPERATURE
with
TC_E
sensor of channel
N
in
the set measurement unit (x10).
1027 +
200 x (
N
-1)
SW
Higher alarm threshold for temperature with TC_E sensor of channel N in
the set measurement unit (x10).
1028 +
200 x (
N
-1)
SW
Channel
N
lower alarm threshold in
mV
(x10). Only if channel
N
is con-
figured as
0…1 V
input.
1029 +
200 x (
N
-1)
SW
Channel
N
higher alarm threshold in mV (x10). Only if channel
N
is con-
figured as 0…1 V input.
1030 +
200 x (
N
-1)
SW
Channel
N
lower alarm threshold in
mV
(x100). Only if channel
N
is con-
figured as
0…50 mV
input.
1031 +
200 x (
N
-1)
SW
Channel
N
higher alarm threshold in mV (x100). Only if channel
N
is
configured as
0…50 mV input.
1032 +
200 x (
N
-1)
SW
Channel
N
lower alarm threshold in
mA
(x100). Only if channel
N
is con-
figured as 4…20 mA input.
1033 +
200 x (
N
-1)
SW
Channel
N
higher alarm threshold in mA (x100). Only if channel
N
is
configured as 4…20 mA input.
1034 +
200 x (
N
-1)
SW
Channel
N
lower alarm threshold in
%
. Only if channel
N
is configured
as potentiometric input.
1035 +
200 x (
N
-1)
SW
Channel
N
higher alarm threshold in
%
. Only if channel
N
is configured
as potentiometric input.
1036 +
200 x (
N
-1)
SW
Lower alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped 0…1 V input.
1037 +
200 x (
N
-1)
SW
Higher alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped 0…1 V input.
1038 +
200 x (
N
-1)
SW
Lower alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped 0…50 mV.
1039 +
200 x (
N
-1)
SW
Higher alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped 0…50 mV.
1040 +
200 x (
N
-1)
SW
Lower alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped 4…20 mA.
1041 +
200 x (
N
-1)
SW
Higher alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped 4…20 mA.
1042 +
200 x (
N
-1)
SW
Lower alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped potentiometric input.
1043 +
200 x (
N
-1)
SW
Higher alarm threshold expressed as value of the quantity associated to
channel
N
when the channel is configured as mapped potentiometric input.
Summary of Contents for Delta OHM HD50 Series