Signet 8250-2 Level Transmitter

CAUTION!

•  Remove power to unit before wiring 

input and output connections.

•  Follow instructions carefully to avoid 

personal injury.

Signet 8250-2 Level Transmitter

English

Contents

1. Description
2. Speci

fi

 cations

3. Panel installation
4. Electrical Connections
5. System con

fi

 guration

Signet Level

Transmitter

Level

+10.00 ft

Relay 1 

Relay 2 

ENTER

1. Description

ProcessPro transmitters are available in two styles: panel mount and 

fi

 eld mount. The panel mount is supplied with the necessary 

hardware to install the transmitter. This manual includes complete panel mounting instructions.

Field mounting requires one of two separate mounting kits. The 3-8052 integral kit joins sensor and instrument together into a single 
package. The 3-8050 Universal kit enables the transmitter to be installed virtually anywhere.

Detailed instructions for integral mounting or other 

fi

 eld installation options are included with the 3-8052 Integral kit or the 3-8050 

Universal kit.

General

Compatible Sensors: 

Signet 2450 Pressure Sensor (S

3

L)

Signet 2250 Level Sensor (S

3

L)

     

Other 3rd party sensors with 4 to 20 mA 

output (via Model 8058)

Materials:
• Case:  

PBT

•  Panel case gasket: 

Neoprene

•  Window:  

Polyurethane-coated polycarbonate

•  Keypad: 

Sealed silicone rubber, 4-button

Weight:  

Approx. 325 g (12 oz.)

Display:
•  Alphanumeric 

2 x 16 LCD

•  Display update rate: 

1 second

•  Contrast: 

User selected, 5 levels

Electrical

Power supply: 

12-24 VDC ±10% regulated,
250 mA max current

Sensor power: 

5 VDC ±1% @ 25 ºC, regulated

  2-wire system: 

1.5 mA maximum current

  4-wire system: 

20 mA maximum current

Current output:
•  4 to 20 mA, isolated, fully adjustable and reversible
•  Max loop impedance:    50 

Ω

 max. @ 12 V

   

325 

Ω

 max. @ 18 V

   

600 

Ω

 max. @ 24 V

•  Update rate:    

300 ms

•  Output accuracy:  

±0.03 mA

Relay outputs (2 sets mechanical SPDT contacts):

•  Software supports 2 additional relays via optional external relay module

Note:

 When using the 8059-4 or -4AC, only relays 1 and 2 can be 

utilized with the level instrument.

•  Maximum voltage rating:

   

5 A @ 30 VDC, or 5 A @ 250 VAC, resistive load

•  Programmable for High or Low setpoint or for Window range, 

with adjustable hysteresis

•  May be disabled if not used

•  Time delay: 

 Programmable from 0 s to 6400 s

Environmental:

•  Operating temperature:  -10 °C to 70 °C (14 °F to 158 °F) 

•  Storage temperature: 

-15 °C to 80 °C (5 °F to 176 °F)

•  Relative humidity: 

0 to 95%, non-condensing

•  Maximum altitude: 

2000 m (6562 ft)

•  Enclosure: 

 

NEMA 4X/IP65 front

Standards and Approvals:

•  CE, UL listed

• Immunity: 

 

EN50082-2

• Emissions: 

 

EN55011

• Safety: 

 

EN61010

•  Manufactured under ISO 9001 for Quality, ISO 14001 for

  Environmental Management and OHSAS 18001 for

  Occupational Health and Safety.

  China RoHS (Go to www.gfsignet.com for details)

  Declaration of Conformity according to FCC Part 15

  This device complies with Part 15 of the FCC rules.

  Operation is subject to the following two conditions:

  (1) This device may not cause harmful interference, and,

  (2) This device must accept any interference received, including

  interference that may cause undesired operation.

2. Specifi cations

Dimensions

3-8250.090-2 

Rev. H  01/13 

English

3-8250.090-2

6. View menu
7. Editing procedure
8. Calibrate menu
9. Options menu
10. Troubleshooting

92 mm 
(3.6 in.) 

97 mm 

(3.8 in.) 

56 mm  
(2.2 in.) 

41 mm  
(1.6 in.

Optional 
Rear 
Cover 

 
 
 

96 mm 

(3.8 in.) 

96 mm 
(3.8 in.) 

106 mm 
(4.18 in.)

82 mm
(3.23 in.)

SIDE VIEW

Field Mount w/

8052 Integral kit

107 mm  

(4.2 in.) 

96 mm 

(3.8 in.) 

Panel Mount

SIDE VIEW

FRONT VIEW

Field Mount &

Panel Mount

SIDE VIEW

Field Mount w/

8050 Universal base

Summary of Contents for Signet 3-8250-2

Page 1: ...ble and reversible Max loop impedance 50 max 12 V 325 max 18 V 600 max 24 V Update rate 300 ms Output accuracy 0 03 mA Relay outputs 2 sets mechanical SPDT contacts Software supports 2 additional rela...

Page 2: ...ure instrument temporarily with tape from front or grip from rear of instrument DO NOT RELEASE 5 Press quick clips outward and remove 2 1 Terminals 11 13 Digital S3 L The 2450 sensor and External Rela...

Page 3: ...el 1 4 to 20 mA in Channel 2 4 to 20 mA in System Pwr Loop System Pwr Loop AUX Power AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power Loop Input 4 to 20 mA System Pwr Loop System Pwr Loop...

Page 4: ...menu if the sensor is located at Z Level L The distance from Z to surface of fluid displayed as Level by transmitter L 0 O 0 Z SLOC L 0 O 0 Z SLOC L 0 SLOC O 0 Z 2450 Pressure Sensor Location and Offs...

Page 5: ...ted at each transition point in the vessel shape for example at custom point 9 where the shape changes from a cylinder to a cone The more complex sections should be defined with more points Notice tha...

Page 6: ...to change display selection Output settings cannot be edited from the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no key is pressed for 10 minut...

Page 7: ...g Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Cod...

Page 8: ...L Single point calibration for Level Reset LVL to Factory Cal Yes Reset Level to original factory calibration Set LVL entry is erased No Return to menu do not reset Level Loop Source LVL Select the so...

Page 9: ...for relay response Relay will be activated only if the source value exceeds the setpoint for this time period Relay settings will repeat for Relay 2 and for External Relays External Relays require th...

Page 10: ...t Test Relay 1 Press UP or DOWN keys to manually toggle the state of Relay 1 Display Factory settings shown Description VOL Shape Vert Cylinder Select the shape of the vessel where Sensor is located V...

Page 11: ...iew all custom points and reset values so each point is greater than the preceding point CHK SENSOR Problem with the sensor during different modes of operation 1 Wiring problem AUXILIARY POWER was not...

Page 12: ...upply Note When using the 8059 4 or 8059 4AC only relays 1 and 2 can be utilized with the flow instrument Accessories Mfr Part No Code Description 3 8050 159 000 184 Universal mounting kit 3 8050 395...

Reviews: