Application
settings:
Factory Set
2551 & 2552
1
Flow Units
m
m, ft, m
3
, L, ft
3
, US Gal, Imp. Gal, Acre in.
2
Time Base
sec
Sec, Min, Hour, Day
3
Pipe ID (Inside Diameter) *
44.0
0 - 5000
4
Pipe ID Units
mm
mm, in.
5
K-Factor Units
Pulses / Liter
Pulses / Liter, Pulses / Gallon
6
K-Factor *
65.76670
0.000100 - 999999.1
See Magmeter manual.
Available at
www.gfps.com
7
Averaging (in seconds)
14
1
/
10
, ¼, ½, 1, 1½, 3, 7, 14, 25, 50, 100
8
Sensitivity (%)
25
100, 50, 30, 25, 20, 15, 10, 8, 5, 2
9
Noise Rejection (Hz)
60
50 or 60
10
Low Flow Cut Off (% of full scale)
0
0 to 20% Full Scale
Loop
Output settings:
11
4 mA Set Point (Flow Units / Time Base)
0.00000
0.00000 - 999999.00000
12
20 mA Set Point (Flow Units / Time Base)
5.00000
Write
or
Save
settings:
13a
or
13b
Click “Write” to copy these settings to the product.
Click “Save” to save these settings to a local computer file for later use.
14
To use a saved file (from 13b):
1. Click “Load”
2. Navigate to the saved file
3. Select “Open”
4. Click “Write”
5. Click “Read” to confirm
2551 & 2552 Operation
*
NOTE
: A proper re-span of the 4 to 20 mA Loop will also require the correct internal pipe ID and K-factor, as both are used to find the
effective velocity of the pipe.
8
GF 0252 Configuration Tool
Summary of Contents for Signet 0252
Page 11: ...258X Operation 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 11 GF 0252 Configuration Tool...
Page 13: ...258X Calibration 6 7 8 9 10 11 13 GF 0252 Configuration Tool...
Page 19: ...2751 Calibration 5 6 7 8 9 10 11 12 19 GF 0252 Configuration Tool...
Page 20: ...2751 Calibration 13 14 15 16 17 20 GF 0252 Configuration Tool...
Page 22: ...9900 Operation 2 3 5a 5b General Software Operation pg 7 22 GF 0252 Configuration Tool...