background image

9900 Operation

Initiating Communication with the 9900:

1a

Factory Configured 9900 (new or reset):

1. If the display reads "PUSH Enter SELECT SENSOR" the 9900 is ready for communication.
2. Proceed to step 2 below.

1b

Previously configured 9900:

1. Press and hold 

ENTER

 for 3 seconds. The display will change to the MENU mode.

2. Press ▲ once. The OPTION menu will flash. Press 

ENTER

3.  The CONTRAST setting will be displayed. 

 

Press ▲ twice (Gen II, III, IV) or press ▲ once (Gen I) to display  REMOTE SETUP.

4. Press ► to edit  REMOTE SETUP. If required, enter the security code.
5. Press ▲ to change the flashing NO to YES. Press 

ENTER

 to confirm change.

6.  REMOTE SETUP should be flashing, indicating the 9900 is ready for communication with the 0252 Tool.

Set Instrument Type:

2

Select sensor type to be wired to the 9900 from the 

 

drop-down menu at the top of the screen.

Flow, pH, ORP, Conductivity, Pressure, Level, 

Temperature, 4 to 20 mA Input, Salinity

Application

 settings:

3

Select the Input, Calibration, Loop, Relay, or Option tabs to choose the desired menu for the selected sensor.

4

Refer to the 9900 manual for details pertaining to specific settings for each sensor type and menu item.
Available at 

www.gfps.com

. Click Products > Multi-Parameter Instruments > 9900 Transmitter

Write

 or 

Save

 settings:

5a

or

5b

Click “Write” to copy these settings to the product.

Click “Save” to save these settings to a local computer file for later use.

6

To use a saved file (from 5b):
1. Click “Load”
2. Navigate to the saved file
3. Select “Open”
4. Click “Write”
5. Click “Read” to confirm

When configuration is complete:

7

Disconnect power from the 9900.

8

Disconnect the 0252 Tool from the 9900.

9

Reconnect the sensor or reinstall the Direct Conductivity/Resistivity Module.

10

Reconnect Power to the 9900.

  To configure an additional 9900 Transmitter with the same settings:

11

Click "Save" to save these settings to a local computer file.

12

Wire another 9900 as shown on page 7.

13

Initiate communication with the 9900 via step 1a or 1b above.

14

Load the saved settings via step 6 above.

21

GF 0252 Configuration Tool

Summary of Contents for Signet 0252

Page 1: ...ngs to factory default condition Calibrate 258X FlowtraMag Full Bore Magmeter 2610 Dissolved Oxygen Sensor and pH ORP sensors using the 2751 Smart Sensor Electronics Microsoft and Windows are register...

Page 2: ...Blue Indicator DATA COMMUNICATION Input connections 3 terminal connectors max 14 AWG Electrical Communication rate Maximum 19 2 kbs Input power Supplied by USB interface Output power 5 VDC 5 Power con...

Page 3: ...the drop down menu Supported languages English French German Spanish Italian Portuguese Chinese 5 Click Save to set language preference Caution Managed systems and network systems may have security m...

Page 4: ...ndows PC Black Red White 1 2 3 4 White Red Black S USB GND Data 5V out USB GND Data 5V out Windows PC Windows PC Black Red White 1 2 3 4 White Red Black S USB GND Data 5V out USB GND Data 5V out Windo...

Page 5: ...ire 1 Additional wire required Brown Black White Blue White Blue Wire Nut To VDC To GND Wire 3 Wire 2 USB GND Data 5V out Windows PC Brown Black White Blue USB GND Data 5V out Windows PC Isolated 24 V...

Page 6: ...ower Supply 12 to 32 VDC Brown Blue Green No connection CAUTION Do not connect power directly to the 0252 Configuration Tool Improper power supply wiring can cause damage to the 0252 hardware and comp...

Page 7: ...reset the connected device to a factory default condition NOTE Performing the above reset to factory default condition will not change the input type on the 9900 Transmitter NOTE Certain sensors 2250...

Page 8: ...ut Off of full scale 0 0 to 20 Full Scale Loop Output settings 11 4 mA Set Point Flow Units Time Base 0 00000 0 00000 999999 00000 12 20 mA Set Point Flow Units Time Base 5 00000 Write or Save setting...

Page 9: ...allow the Magmeter to override AVERAGING and jump to a new flow rate immediately 2551 maximum range is 10 m s See Magmeter manual for an explanation of Averaging and Sensitivity www gfps com Noise Rej...

Page 10: ...Select Output modes 4 to 20 mA as either Active or Passive S L or Frequency output Note Setting the 258X to frequency will prevent the use of the 0252 tool You will need to change the 258X back to S...

Page 11: ...258X Operation 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 11 GF 0252 Configuration Tool...

Page 12: ...low Rate settings 6 Wait for flow reading to stabilize then enter correct flow and Click Set Flow 7 Cancel Flow Rate Calibration and return to Calibration screen Volumetric settings 8 Start Volumetric...

Page 13: ...258X Calibration 6 7 8 9 10 11 13 GF 0252 Configuration Tool...

Page 14: ...Water Salinity Value for Salt Compensation 0 Fresh Water Loop Output settings 5 Select Measurement Dissolved Oxygen or Temperature for 4 to 20 mA Output 6 Set 4 mA Set Point 7 Set 20 mA Set Point Inf...

Page 15: ...ated Water click Start to begin the Calibration 4 Once probe reading is stable click Continue Second Point settings 5 With probe in 0 Saturated Water click Start to begin the second point Calibration...

Page 16: ...ss Impedance Set Point for Alarm pH 10 Glass Impedance Update Timer pH Information settings 11 Click Get Data to Update Sensor Data 12 Electrode Serial Number pH or ORP 13 Electrode Part Number pH or...

Page 17: ...2751 Operation 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 17 GF 0252 Configuration Tool...

Page 18: ...Click Next for two point calibration 9 Click End to complete one point calibration 10 To cancel calibration click Cancel and return to Calibration Screen Temperature Calibration settings 11 Start Cali...

Page 19: ...2751 Calibration 5 6 7 8 9 10 11 12 19 GF 0252 Configuration Tool...

Page 20: ...2751 Calibration 13 14 15 16 17 20 GF 0252 Configuration Tool...

Page 21: ...on settings 3 Select the Input Calibration Loop Relay or Option tabs to choose the desired menu for the selected sensor 4 Refer to the 9900 manual for details pertaining to specific settings for each...

Page 22: ...9900 Operation 2 3 5a 5b General Software Operation pg 7 22 GF 0252 Configuration Tool...

Page 23: ...the maximum interval is 86400 seconds 24 hours Example If the Log Interval is set to 60 seconds the 0252 will record the temperature once every minute 4 The 0252 saves data files in csv format The ma...

Page 24: ...ce visit our website www gfps com Or call in the U S 800 854 4090 For the most up to date information please refer to our website at www gfps com 3 0252 090 Rev 3 01 22 English Georg Fischer Signet LL...

Reviews: