With the following parameters, you can perform a specific control for the hot runners (hot.runners).
The main functions are:
FAULT ACTION POWER
You can decide what power to supply in case of broken probe.
FAP is the reference power for parameter FAP.
Average power is the average power calculated in the last 300 sec.
The alarm reset and reference power update take place only at switch-on or after a setpoint change.
The alarm is not activated if the control (Ctr) is ON/OFF type, during Selftuning and in Manual.
HOT RUNNERS CONTROL
POWER ALARM
The alarm signals any power changes (OuP) after the
process variable
(PV) has stabilized on the setpoint (SP). The
time beyond which the process variable is considered stable is 300 sec (always on with hot runners).
The reference power update take place only at switch-on or after a setpoint change.
If the process variable leaves the stabilization band after the first stabilization, this does not influence the alarm.
In case of SBR:
- if the PV has not yet stabilized, either the average power over the last 5 minutes or FAP power is supplied (depending on
the setting of the HOT parameter).
- if the PV has stabilized the average power over the last 5 minutes is supplied.
Function:
If necessary, assign an output (rL.2...6) for the power alarm.
Set the band (b.ST) within which the process variable is considered stable after 300 sec. have elapsed.
Set the band (b.PF) outside which the alarm is activated after time PF.t has elapsed.
The reference power is the active power after 300 sec. have elapsed.
The alarm reset and reference power update take place only at switch-on or after a setpoint change.
265
xot
R/W
Select hot runner functions
0
Read state
26
bit
STATE OF HB ALARM
OR POWER_FAULT
OFF = Alarm off
ON = Alarm on
R
228
fa.p
R/W
Fault action power (supplied in
conditions of broken probe)
-100.0 ..100.0 %
0.0
80
State of power alarm
(hot runners)
OFF = Alarm off
ON = Alarm on
R
Table of hot runner functions
Fault action
Enable
power if PV is
Enable
hot runners
not stabilized
preheating softstart
0
FA.P
1
X
Average power
2
FA.P
3
X
FA.P
4
FA.P
X
5
X
Average power
X
6
FA.P
X
7
X
FA.P
X
+8 enable GS.2
FA.P – see alarm for probe in short or connection error (SBR-ERR)