Maximum error of non linearity for thermocouples (Tc), resistance thermometer (PT100)
Type Type of probe
Scale
Without dec. point
With dec. point
0
TC J
°C
0/1000
0.0/999.9
1
TC J
°F
32/1832
32.0/999.9
2
TC K
°C
0/1300
0.0/1300.0
3
TC K
°F
32/2372
32.0/999.9
4
TC R
°C
0/1750
0.0/999.9
5
TC R
°F
32/3182
32.0/999.9
6
TC S
°C
0/1750
0.0/999.9
7
TC S
°F
32/3182
32.0/999.9
8
TC T
°C
-200/400
-199.9/400.0
9
TC T
°F
-328/752
-199.9/752.0
28
TC
custom
custom
custom
29
TC
custom
custom
custom
Tc type:
J, K
error < 0.2% f.s.
S, R range 0...1750°C: error < 0.2% f.s. (t > 300°C)
For other ranges: error < 0.5% f.s.
T error < 0.2% f.s. (t > -150°C)
And inserting a custom linearization
E, N, L
error <0.2% f.s.
B
range 44...1800°C; error < 0.5% f.s. (t > 300°C)
range 44.0...999.9; error f.s.(t>300°C)
U
range -200...400; error < 0.2% f.s. (for t > -100°C)
For other ranges; error <0.5% f.s.
G error < 0.2% f.s. (t > 300°C)
D error < 0.2% f.s. (t > 200°C)
C
range 0...2300;
error < 0.2% f.s.
For other ranges; error < 0.5% f.s.
JPT100 and PT100
error < 0.2% f.s.
The error is calculated as deviation from theoretical value with % reference
to the full-scale value expressed in degrees Celsius (°C).
TC SENSOR
Type Type of probe
Scale
Without dec. point
With dec. point
30
PT100
°C
-200/850
-199.9/850.0
31
PT100
°F
-328/1562
-199.9/999.9
32
JPT100
°C
-200/600
-199.9/600.0
33
JPT100
°F
-328/1112
-199.9/999.9
SENSOR: RTD 3-wires
Type Type of probe
Scale
Without dec. point
With dec. point
34
0...60 mV
Linear
-1999/9999
-199.9/999.9
35
0...60 mV
Linear
Custom linearization
Custom linearization
36
12...60 mV
Linear
-1999/9999
-199.9/999.9
37
12...60 mV
Linear
Custom linearization
Custom linearization
SENSOR: 60mV voltage
Type Type of probe
Scale
Without dec. point
With dec. point
38
0...20 mA
Linear
-1999/9999
-199.9/999.9
39
0...20 mA
Linear
Custom linearization
Custom linearization
40
4...20 mA
Linear
-1999/9999
-199.9/999.9
41
4...20 mA
Linear
Custom linearization
Custom linearization
SENSOR: 20mA current
Type Type of probe
Scale
Without dec. point
With dec. point
42
0...1 V
linear
-1999/9999
-199.9/999.9
43
0...1 V
linear
Custom linearization
Custom linearization
44
200 mV..1 V
linear
-1999/9999
-199.9/999.9
45
200 mV..1 V
linear
Custom linearization
Custom linearization
SENSOR: 1V voltage
Type Type of probe
Scale
Without dec. point
With dec. point
46
Cust. 20mA
-
-1999/9999
-199.9/999.9
47
Cust. 20mA
-
Custom linearization
Custom linearization
48
Cust. 60mV
-
-1999/9999
-199.9/999.9
49
Cust. 60mV
-
Custom linearization
Custom linearization
50
PT100-JPT
-
custom
custom
SENSOR: Custom
400
tYP.
R/W
Probe type, signal, enable, custom
linearization and main input scale
0
Probes and sensors
Table of probes and sensors
99 Input off
403
dP.S
R/W
Decimal point position for input scale
0
Format
0
xxxx
1
xxx.x
2
xx.xx (*)
3
x.xxx (*)
(*) Not available for TC, RTD probes
Specifies the number of decimal figures used to represent the input signal value: for
example, 875.4 (°C) with dP.S = 1.
Decimal point table
Scale limits
401
Lo.S
R/W
Minimum scale limit of main input
0
min...max scale
of input selected
in tyP
Engineering value associated to minimum level of the signal generated by the sensor
connected to the input: for example 0 (°C) with type K thermocouple.
402
xi.S
R/W
Maximum scale limit of main input
1000
min...max scale
of input selected
in tyP
Engineering value associated to maximum level of the signal generated by the sensor
connected to the input: for example 1300 (°C) with type K thermocouple.
Setting the offset
519
23
ofs.
R/W
Offset correction for main input
-999...999
scale points
0
Lets you set a value in scale points that is algebraically added to the value measured by
the input sensor.
Calibrate the UCA inputs by means of the
GFX-OP terminal.
The procedure is described in the GFX-OP
manual.