27
80415F_MSW_GFX4-IR_05-2019_ENG
Alarms hysteresis
27
187
XY.1
R/W
Hysteresis
for alarm 1
± 999
Scale points
- 1
0...999 sec. Se +32 in A1.t
0...999 min. Se +64 in A1.t
59
XY.4
R/W
Hysteresis for alarm 4
± 999
Scale points
- 1
0...999 sec. Se +32 in A4.t
0...999 min. Se +64 in A4.t
53
189
XY.3
R/W
Hysteresis for alarm 3
± 999
Scale points
- 1
0...999 sec. Se +32 in A3.t
0...999 min. Se +64 in A3.t
30
188
XY.2
R/W
Hysteresis for alarm 2
± 999
Scale points
- 1
0...999 sec. Se +32 in A2.t
0...999 min. Se +64 in A2.t
Reference variables
215
a1.r
R/W
Select reference variable alarm 1
0
216
A2.r
R/W
Select reference variable alarm 2
217
A3.r
R/W
Select reference variable alarm 3
218
A4.r
R/W
Select reference variable alarm 4
Variable to be compared
Reference setpoint
0
PV (process variable)
AL
1
in.tA1
AL
(In.tA1 OR In.tA2 OR In.tA3
WITH 3-PHASE LOAD)
2
In.tV1
AL
(In.tV1 OR In.tV2 OR In.tV3
WITH 3-PHASE LOAD)
3
SPA (active setpoint)
AL (absolute only)
4
PV (process variable)
AL [deviation only and
referred to SP1
(with multiset function)
5
In.2 auxiliary input
AL
N.B. for codes 1, 2 and 5, the reference to the alarm is in scale points
and not to the decimal point (d.P)
0
0
0
Table of alarm reference setpoints
Alarm setpoints
12
475 - 177
AL.1
R/W
Alarm setpoint
1 (scale points)
500
13
476 - 178
AL.2
R/W
Alarm setpoint 2 (scale points)
100
14
52 - 479
AL.3
R/W
Alarm setpoint 3 (scale points)
700
58
480
AL.4
R/W
Alarm setpoint 4 (scale points)
800
-1999...9999
scale points
-999...999 If symmetrical alarm
0...999 If symmetrical and relative alarm
-1999...9999
scale points
-999...999 If symmetrical alarm
0...999 If symmetrical and relative alarm
-1999...9999
scale points
-999...999 If symmetrical alarm
0...999 If symmetrical and relative alarm
-1999...9999
scale points
-999...999 If symmetrical alarm
0...999 If symmetrical and relative alarm