34
80415F_MSW_GFX4-IR_05-2019_ENG
Read state
26
bit
HB ALARM STATE OR
POWER_FAULT
OFF = Alarm off
ON = Alarm on
R
504
R
HB alarm states ALSTATE_HB (for
3-phase loads)
bit
0
HB TA2 time ON
1
HB TA2 time OFF
2
HB alarm TA2
3
HB TA3 time ON
4
HB TA3 time OFF
5
HB alarm TA3
Table of HB alarm states
512
R
States of alarm ALSTATE
bit
4
HB alarm time ON
5
HB alarm time OFF
6
HB alarm
Table of alarm states ALSTATE
76
bit
State of HB alarm
phase 1
R
77
bit
State of HB alarm
phase 2
with 3-phase loads
R
78
bit
State of HB alarm
phase 3
with 3-phase loads
R
744
xb.tr
R
HB alarm setpoint as function
of power on load
318
R
State of alarms ALSTATE IRQ
bit
0
State AL.1
1
State AL.2
2
State AL.3
3
State AL.4
4
State AL.HB (if 3-phase or phase 1/2/3)
or Power Fault
5
State AL.HB PHASE 1 (if 3-phase)
6
State AL.HB PHASE 2 (if 3-phase)
7
State AL.HB PHASE 3 (if 3-phase)
States of alarm table