54
80415F_MSW_GFX4-IR_05-2019_ENG
SOFTSTART
If enabled, this function partializes power based on a percentage of time elapsed since instrument switch-on compared
to the set time of 0.0 ... 500.0 min (“SoFt” parameter CFG phase). Softstart is an alternative to selftuning and is activated after
each instrument switch-on. Softstart is reset when switching to manual.
Read state
147
SOF
R/W
Softstart time
0.0 ...500.0 min
0.0
63
bit
STATE SOFTSTART
OFF = Softstart in Stop
ON = Softstart in Start
R
START MODE
699
P.ONT
R/W
Start modes at Power-On
0* Function at previous state
1 Software shutdown
2 Software startup
(*) digital input states always have priority
68
bit
STATE OF DIGITAL
INPUT 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
STATE OF DIGITAL
INPUT 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
See: Table of digital input functions
Read state
0
bit
SELFTUNING STATE
OFF = Selftuning in Stop
ON = Selftuning in Start
R
296
R
Autotuning and selftuning enable state
(FLG_PID)
bit
3
Selftuning on
6
Autotuning on
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
0
Autotuning
Selftuning
Softstart
continuous
0
NO
NO
NO
1
YES
NO
NO
2
NO
YES
NO
3
YES
YES
NO
4
NO
NO
YES
5
YES
NO
YES
Autotuning One-shot
8*
WAIT
NO
NO
9
GO
NO
NO
10*
WAIT
YES
NO
11
GO
YES
NO
12*
WAIT
NO
YES
13
GO
NO
YES
Selftuning, autotuning, softstart table
(*) +16 with automatic switching in GO if PV-SP > 0.5% f.s.
+32 with automatic switching in GO if PV-SP > 1% f.s.
+64 with automatic switching in GO if PV-SP > 2% f.s.
+128 with automatic switching in GO if PV-SP > 4% f.s.
30
bit
RESTART
SOFTSTART
OFF = -
ON = Restart Softstart
R/W