AFE200 • Instruction Manual
95
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
9.39
1614 Analog inp 1X bottom
cnt
INT16
-16384
-32768
+32767 ERW
9.50
1664 Analog inp 2X bottom
cnt
INT16
-16384
-32768
+32767 ERW
Setting of an offset value to algebrically add to the relative analog input of the expan-
sion card.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
9.40
1616 Analog inp 1X offset
cnt
INT16
0
-32768
+32767 ERW
9.51
1666 Analog inp 2X offset
cnt
INT16
0
-32768
+32767
ERW
Setting of an offset value to algebrically add to the relative analog input of the expan-
sion card.
0
10V
100%
Analog inp x offset
{
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
9.41
1618 Analog inp 1X gain
FLOAT
1.0
-10.0
10.0
ERW
9.52
1668 Analog inp 2X gain
FLOAT
1.0
-10.0
10.0
ERW
This parameter contains the value of the multiplier factor to apply to the analog refer-
ence of the expansion card calculated using the
Analog inp gain tune
function.
Example :
An external analog reference only reaches a maximum of 9.8V instead of 10V. 1.020
(10V : 9.8V) is entered as the
Analog inp x gain
parameter.
The same result can be achieved using the
Analog inp x gain
tune function. This pa-
rameter can be selected from the keypad menu. The maximum analog value available
(in this case 9.8V) must be present on the terminal, with positive polarity. Press the
Enter
key on the keypad to start analog reference self-tuning.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
9.42
1626 Sorg segno ing an 1X
LINK
16
6000
0
16384 ERW
9.53
1676 Sorg segno ing an 2X
LINK
16
6000
0
16384 ERW
L�DIGSEL2
Selection of the origin (source) for the signal to be assigned to the relative digital input
for selecting the sign of the relative analog reference signal. The functions that can be
associated with the digital outputs are listed in the “L_DIGSEL2” selection list.