5.1 Power section
5.1.1 Cable Cross Section
Sizes
AFE200-
Terminals: C - D - U - V - W
Maximum Cable Cross Section (flexible conductor)
Recommended stripping
Tightening torque (min)
(mm
2
)
AWG
(mm)
(Nm)
3220
16
6
14
1,5 ... 1,7
4450
35
2
18
2,4 ... 4,5
5900
95
4/0
23
14
61320
240
500
40
40
Bars: C - D - U - V - W
Recommended cable cross-section
Recommended stripping
Tightening torque (min)
(mm
2
)
AWG / kcmil
(mm)
(Nm)
71600
2 x 100
2 x AWG 4/0
M10
50
72000
2 x 100
2 x AWG 4/0
M10
50
72500
2 x 150
2 x kcmil 300
M10
50
73150
2 x 185
2 x kcmil 350
M10
50
73550
2 x 185
2 x kcmil 350
M10
50
Sizes
AFE200-
Terminals:
on mechanical cabinet
Cable Cross Section
Lock screw
diameter
Recommended
terminal
Tightening torque
(mm
2
)
AWG / kcmil
(mm)
(mm)
(Nm)
3220 ... 4450
16
AWG 6
M6
Eyelet - Spade
10
5900
50
AWG 1/0
M6
Eyelet - Spade
10
61320
120
250 kcmil
M8
Eyelet
24
71600
150
300 kcmil
M10
Eyelet
50
72000
150
300 kcmil
M10
Eyelet
50
72500
150
300 kcmil
M10
Eyelet
50
73150
185
350 kcmil
M10
Eyelet
50
73550
185
350 kcmil
M10
Eyelet
50
Sizes
AFE200-
Bars: C - D - U - V - W
Recommended cable cross-
section
Recommended
stripping
Tightening torque
(min)
(mm
2
)
AWG / kcmil
(mm)
(Nm)
400kW
72000-KXX-4-MS 04
2 x 100
2 x AWG 4/0
M10
(U,V,W=M12)
50
(M10)
/ 75
(M12)
72000-XXX-4-SL
2 x 100
2 x AWG 4/0
M10
(U,V,W=M12)
50
(M10)
/ 75
(M12)
500kW
72500-KXX-4-MS 05
2 x 150
2 x kcmil 300
M10
(U,V,W=M12)
50
(M10)
/ 75
(M12)
72500-XXX-4-SL
2 x 150
2 x kcmil 300
M10
(U,V,W=M12)
50
(M10)
/ 75
(M12)
630kW
73150-KXX-4/4A-MS 06
2 x 185
2 x kcmil 350
M10
(U,V,W=M12)
50
(M10)
/ 75
(M12)
73150-XXX-4/4A 4-SL
2 x 185
2 x kcmil 350
M10
(U,V,W=M12)
50
(M10)
/ 75
(M12)