AFE200 • Instruction Manual
67
The reactive current reference is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.8
284
Active current
A
FLOAT
16/32
0.0
0.0
0.0
ER
The active current value currently in use is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.9
286
Reactive current
A
FLOAT
16/32
0.0
0.0
0.0
ER
The reactive current value currently in use is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.10
256
Phase U voltage
V
FLOAT
16/32
0.0
0.0
0.0
R
The phase U voltage is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.11
258
Phase V voltage
V
FLOAT
16/32
0.0
0.0
0.0
R
The phase V voltage is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.12
260
Phase W voltage
V
FLOAT
16/32
0.0
0.0
0.0
R
The phase W voltage is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.13
248
Power factor
FLOAT
0.0
0.0
0.0
ER
The power factor value (cosφ) is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.14
262
Output power
kW
FLOAT
16/32
0.0
0.0
0.0
ER
The value of the power generated into the mains is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.15
264
Output energy
kWh FLOAT
0.0
0.0
0.0
ER
The value of the energy generated onto the mains is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
1.16
368
Drive overload accum
perc
UINT16 16/32
0
0
100
ER
The drive overload level is displayed. An instantaneous overload of 180% of the drive
rated current is allowed for 0.5s. The thermal image I²t adjusts the drive output current
thresholds. During normal operation, the instantaneous output current value can reach
180% of the drive rated current. After 0.5s at 180%, the output current threshold is
reduced to 150%. When the overload level
PAR 368 Drive overload accum
reaches
100%, the output current threshold is reduced to 100% of the rated current, and stays
at that value until the I²t integrator cycle is complete. At this point the 180% instantane-
ous overload is re-enabled.