126
AFE200 • Instruction Manual
Enabling of automatic restart after the desaturation alarm
Desaturation [5]
. This
alarm indicates a short circuit between the phases of the power bridge.
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.22
4612 Desat restart time
ms
UINT16
2000
1000
10000 ERW
Setting of the time within which the
Desaturation [5]
alarm must be reset in order to
perform automatic restart. (Time with alarm signal 1000 msec).
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.23
4620 IOverC restart
ENUM
Disable
0
1
ERW
Enabling of automatic restart after the AFE product
Overcurrent [4]
alarm. This alarm
indicates an overcurrent (or short circuit between phases or towards the ground).
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.24
4622 IOverC restart time
ms
UINT16
2000
1000
10000 ERW
Setting of the time within which the
Overcurrent [4]
alarm must be reset in order to
perform automatic restart. (Time with alarm signal 1000 msec).
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.25
4630 OverV restart
ENUM
Disable
0
1
ERW
Enabling of automatic restart after the
Overvoltage [1]
alarm. This alarm indicates an
overvoltage on the intermediate circuit (DC link)
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.26
4632 OverV restart time
ms
UINT16
2000
1000
10000 ERW
Setting of the time within which the
Overvoltage [1]
alarm must be reset in order to
perform automatic restart. (Time with alarm signal 1000 msec).
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.27
4640 UnderV restart
ENUM
Enable
0
1
ERW
Enabling of automatic restart after the
Undervoltage [2]
alarm. This alarm indicates
an undervoltage on the intermediate circuit (DC link)
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.28
4642 UnderV restart time
ms
UINT16
1000
120
10000 ERW
Setting of the time within which the
Undervoltage [2]
alarm must be reset in order to
perform automatic restart. (Time with alarm signal 100 msec).