AFE200 • Instruction Manual
147
10.6 Electrical data
Input voltage (AFE200-...-4/4A) ����������380 - 15% ... 500 +5% V
ac
Input voltage (AFE200-... -6/6A) ���������500 - 10% ... 690 +10% V
ac
Input frequency ����������������������50/60 Hz ±2%
Maximum line voltage unbalance ���������3 %
THd
Input current ��������������������≤ 5%
Cosphi ����������������������������≥ 0.99
Connection to TT and TN Networks �������AFE200-...-4/4A and AFE200-... -6/6A: = Suitable
Connection to IT Networks: �������������AFE200-...-4/4A = Not suitable
AFE200-... -6/6A: = Suitable for sizes (with integrated
EMI filter).
Sizes
AFE200-...-4
AC
input current
DC
output current
f
sw
Switching frequency
Derating factor
Heavy duty
Light duty
Heavy duty
Light duty
Default
(kHz)
Higher
(kHz)
K
v
K
t
K
f
(@ 8
kHz)
K
alt
@ 400 V
ac
(A)
@ 400 V
ac
(A)
@ 650 V
dc
(A)
@ 650 V
dc
(A)
(1)
(2)
(3)
(4)
3220
40
60
43
64
8
-
0.9
0.9
-
1.2
4450
80
100
85
107
8
-
0.9
0.9
-
1.2
5900
160
200
171
213
4
6.8
0.9
0.9
0.7
1.2
61320
230
280
245
298
4
6.8
0.9
0.9
0.7
1.2
71600
280
340
298
363
4
-
0.9
0.9
-
1.2
72000
340
400
363
426
2
4
0.9
0.9
-
1.2
72500
400
500
426
532
2
4
0.9
0.9
-
1.2
73150
500
560
532
597
2
-
0.9
0.9
-
1.2
73550
560
600
597
640
2
-
0.9
0.9
-
1,2
400kW
600
760
640
811
2
-
0.9
0.9
-
1,2
500kW
760
950
811
1012
2
-
0.9
0.9
-
1,2
630kW
950
1060
1012
1129
2
-
0.9
0.9
-
1,2
710kW
1060
1150
1129
1226
2
-
0.9
0.9
-
1,2
900kW
1400
1500
1492
1598
2
-
0.9
0.9
-
1,2
1MW
1500
1730
1598
1846
2
-
0.9
0.9
-
1,2
(1) K
v
: Derating factor for mains voltage at 460V
ac
(2) K
t
: Derating factor for 50°C ambient temperature (1 % each °C above 40°C)
(3) K
f
: Derating factor for higher switching frequency
(4) K
alt
: Derating factor for installation at altitudes above 1000 meters a.s.l.. Value to be applied at each 100 m increase above 1000 m
(up to a maximum of 2000 m).
I.e.: Altitude 2000 m, Kalt = 1,2 *10 = 12% di derating; In derated = 100 - ((12*100)/100) = 88 % In
Sizes
AFE200-...-6
AC
input current
DC
output current
f
sw
Switching frequency
Derating factor
Heavy duty
Light duty
Heavy duty
Light duty
Default
(kHz)
Higher
(kHz)
K
v
K
t
H
eavy
duty
K
t
Light
duty
K
alt
(A)
(A)
(A)
(A)
(6)
(7)
(7)
(8)
71600
150
190
165
210
4
-
1
0.9
0.8
1.2
72000
190
240
210
265
2
-
1
0.9
0.8
1.2
72500
240
300
265
330
2
-
1
0.9
0.8
1.2
73150
300
340
330
375
2
-
1
0.9
0.8
1.2
73550
340
(5)
380
375
420
2
-
1
0.85
0.8
1.2
400kW
360
455
396
500
2
-
1
0.9
0.8
1.2
500kW
455
570
500
627
2
-
1
0.9
0.8
1.2
630kW
570
645
627
711
2
-
1
0.9
0.8
1.2
710kW
645
(5)
720
711
792
2
-
1
0.85
0.8
1.2
900kW
850
920
935
1012
2
-
1
0.9
0.8
1.2
1MW
920
(5)
1050
1012
1265
2
-
1
0.85
0.8
1.2