AFE200 • Instruction Manual
127
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.29
4650 UVRep attempts
UINT16
5
0
1000
ERW
Setting of the maximum number of attempts at automatic restart after the
Undervolt-
age [2]
alarm before a
Mult
Undervoltage [6]
alarm is generated. If this parameter
is set to 1000 an infinite number of attempts are available.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.30
4652 UVRep delay
s
UINT16
240
0
300
ERW
Setting of the time within which, if no automatic restarts are executed after the
Und-
ervoltage [2]
alarm, the attempts counter is reset. In this way the number of attempts
set in
UVRep attempt
are still available.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.31
4670 Optionbus activity
ENUM
Disable
0
2
ERW
Setting of the behaviour of the AFE product in case of an
Opt Bus Fault [16]
alarm
.
0
Ignore
1
Warning
2
Disable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.32
4680 GroundFault thr
perc
FLOAT
10.0
0.0
150.0 ERWS
Setting of the threshold for the ground short circuit alarm
Ground Fault [3]
.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.33
4700 Alarm dig sel 1
ENUM
No alarm
0
40
ERW
15.34
4702 Alarm dig sel 2
ENUM
No alarm
0
40
ERW
15.35
4704 Alarm dig sel 3
ENUM
No alarm
0
40
ERW
15.36
4706 Alarm dig sel 4
ENUM
No alarm
0
40
ERW
Setting of the alarm signal to enable on a digital output. The digital output is selected
using parameters
Alm dig out mon 1÷4
, which can be enabled in the L_DIGSEL1
selection list.
0
No alarm
1
Overvoltage
2
Undervoltage
3
Ground fault
4
Overcurrent
5
Desaturation
6
MultiUndervolt
7
MultiOvercurr
8
MultiDesat
9
Undervolt AC
10
Overvoltage AC
11
Heatsink OT
12
HeatsinkS OTUT
13
Intakeair OT
14
Drive overload
15
Bres overload
16
Opt Bus fault
17
Opt 1 IO fault
18
Opt 2 IO fault
19
Opt Enc fault