GRASSO SYSTEM CONTROL
Kap.6 - 8
638660E_chapter6.doc
01.2003/0
Display message / Explanation
Possible cause of the alarm
Alarm clearance
The oil differential pressure is too
low.
Remove cause of low oil differential
pressure at the compressor.
050 Alarm
(01)
Oil differential
pressure too low
‘dPoil low alarm’ limit is set too
high.
Change ‘dPoil low alarm’ limit to a
suitable value.
This alarm is activated if the oil
difference between the oil pressure
and crankcase pressure or suction
pressure (only if no crankcase
pressure is available) is less than the
’dPoil low alarm’ limit value and the
time delay ’Oil dif start’ and/or ’Oil
dif run’ has expired.
‘Oil dif start’ and/or ‘Oil dif run’
time is set too short.
Change ‘Oil dif start’ and ‘Oil dif run’
times to suitable values.
The differential pressure is too
high.
Remove cause of high differential
pressure in the refrigeration plant.
051 Alarm
(01)
Differential
(Psuc and Pdis)
pressure too high
The configuration is incorrect.
Check the parameter ‘Refrigerant’ and
‘Comp type’ in the configuration
menu.
This alarm is activated if the
calculated differential pressure
exceeds the fixed limit for the
selected compressor type.
The pressure ratio is too high.
Remove cause of high differential
pressure in the refrigeration plant.
052 Alarm
(01)
Pressure ratio
(Psuc and Pdis)
too high
The configuration is incorrect.
Check the parameter ‘Refrigerant’ and
‘Comp type’ in the configuration
menu.
This alarm is activated if the pressure
ratio exceeds the fixed limit for the
selected compressor type.
The suction temperature is too low. Remove cause of high differential
pressure in the refrigeration plant.
053 Alarm
(01)
Suction temperature
too low
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
The sensor is defective.
Replace the sensor.
This alarm is activated if the suction
temperature falls below the fixed
limit for minimum suction
temperature.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
054 Alarm
(01)
Wire failure
suction temperature
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the suction
temperature sensor.
The analogue input module
defective.
Replace the analogue input module.
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......