GRASSO SYSTEM CONTROL
Kap.6 - 20
638660E_chapter6.doc
01.2003/0
Warning message
Possible cause
Warning clearance
The suction temperature is too low. Remove the cause for low suction
temperature in the refrigerating
plant.
112 Warning
(01)
Low suction
temperature
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
suction temperature is less than a
fixed limit value.
The sensor is defective.
Replace the sensor.
The motor speed is too high.
Remove the cause for high motor
speed in the refrigerating plant.
121 Warning
(01)
High motor speed
‘Nmot hi alarm‘ minus ‘High
warning‘ set too high.
Change ‘Nmot hi alarm’ and ‘High
warning’ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
motor speed is higher than the
‘Nmot hi alarm’ minus ‘High
warning’ limit values.
The sensor is defective.
Replace the sensor.
The intermediate temperature at
the low pressure side is too low.
Remove cause of low intermediate
temperature LP in the refrigeration
plant.
124 Warning
(01)
Liquid in compressor
Discharge temperature
(LP) too low
This warning is activated if the
discharge temperature at the low
pressure side (equals intermediate
temperature LP) falls below a fixed
limit value.
The intermediate temperature at
the low pressure side is too high.
Remove cause of high intermediate
temperature LP in the refrigeration
plant.
125 Warning
(01)
Compressor heating
Discharge temperature
(LP) too high
This warning is activated if the
discharge temperature at the low
pressure side (equals intermediate
temperature LP) exceeds a fixed limit
value.
The discharge temperature at the
high pressure side is too low.
Remove cause of low discharge
temperature in the refrigeration
plant.
126 Warning
(01)
Liquid in compressor
Discharge temperature
(HP) too low
This warning is activated if the
discharge temperature at the high
pressure side falls below a fixed limit
value.
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......