Grasso
Refrigeration Division
GRASSO SYSTEM CONTROL
01.2003/ 0
638660E_chapter9.doc
Kap.9 - 3
#
Title
Unit
HotKey
20
Limit values
DIR
Parameters for limiting values
Range
Default setting
Project setting
External temp
Text low alarm
°C
-65,0 ... +65,0
2,0
Low warning
K
+
0,0 ... 10,0
1,0
Low limit
K
+
0,0 ... 10,0
2,0
Decr limit
K
+
0,0 ... 10,0
1,0
Motor speed
Nmot low alarm
rpm
? ... 1000
600
Low warning
rpm
+
0 ... 500
50
Nmot hi alarm
rpm
600 ... ?
1000
High warning
rpm
-
0 ... 500
50
Capacity
Minimum
%
0 ... 100
0
Maximum
%
0 ... 100
100
30
Time values
DIR
Parameters for timer values
Range
Default setting
Project setting
Start to start
s
60 ... 1800
600
Stop to start
s
60 ... 1800
180
Oil dif start
s
1 ... 60
20
Oil dif run
s
1 ... 60
10
Unloaded start
s
5 … 150
20
Motor feedback
s
1 ... 60
10
Pump down time
s
5 ... 21600
300
dTo alarm dly
s
5 ... 40
20
dTm alarm dly
s
5 … 40
40
Run.hours
s
0 ... 99999999
0
35
Unit options
DIR
Parameters for optional values
Default setting
Project setting
Sequence Control:
Value + Parameter
Economiser:
Parameter
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......