Grasso
Refrigeration Division
GRASSO SYSTEM CONTROL
01.2003/ 0
638660E_chapter9.doc
Kap.9 - 5
#
Title
Unit
HotKey
50
Configuration
DIR
Parameters for configuration values
Range
Default setting
Project setting
Sensor scaling:
Discharge pressure
Sensor:
Disch press
Begin (4mA)
bar (a)
0,0 ... 40,0
0,0
End (20mA)
bar (a)
0,0 ... 40,0
25,0
Sensor scaling:
Itermediate pressure
Sensor:
Interm press
Begin (4mA)
bar (a)
0,0 ... 40,0
0,0
End (20mA)
bar (a)
0,0 ... 40,0
25,0
Sensor scaling:
Oil pressure
Sensor:
Oil press
Begin (4mA)
bar (a)
0,0 ... 40,0
0,0
End (20mA)
bar (a)
0,0 ... 40,0
25,0
Sensor scaling:
Crankcase pressure
Sensor:
Crankc press
Begin (4mA)
bar (a)
0,0 ... 40,0
0,0
End (20mA)
bar (a)
0,0 ... 40,0
10,0
Sensor scaling:
Suction temperature
Sensor:
Suction temp
Offset (K)
°C
-10,0 ... 10,0
0,0
Spann (%)
°C
-20,0 ... 20,0
0,0
Sensor scaling:
Discharge temperature
Sensor:
Disch temp
Offset (K)
°C
-10,0 ... 10,0
0,0
Spann (%)
°C
-20,0 ... 20,0
0,0
Sensor scaling:
Intermediate temperature LP
Sensor:
Intm temp LP
Offset (K)
°C
-10,0 ... 10,0
0,0
Spann (%)
°C
-20,0 ... 20,0
0,0
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......