Grasso
Refrigeration Division
GRASSO SYSTEM CONTROL
01.2003/ 0
638660E_chapter9.doc
Kap.9 - 1
LIST OF PARAMETERS
#
Title
Unit
HotKey
5
Actual values
K 06
ACTUAL values of compressor unit data +
remaining times for timers
10
Control settings
K 14
Parameters for control values
Range
Default setting
Project setting
Set Point 1
°C
-65,0 ... +65,0
6,0
Set Point 2
°C
-65,0 ... +65,0
6,0
Neutral zone
K
0,1 ... 10,0
1,0
Prop zone
K
2,0 ... 50,0
15,0
Cap inc (min)
s
15 ... 600
30
Cap inc (max)
15 ... 600
120
Cap dec (min)
s
15 ... 600
20
Cap dec (max)
s
15 ... 600
90
Auto start dly
s
15 ... 1800
30
Pump down
with / without
without
Stop pressure
bar (a)
0,50 ... 8,00
3,00
Boost press
bar (a)
0,0 ... 25,0
3,0
Cor P-zone
K
-10,0 ... 10,0
0,0
Derative fact
K
0,0 ... 10,0
1,0
15
Operating modes
K 15
Parameters for operating modes
Default setting
Project setting
Operating mode
01 Manual
Control on
Suc press
Power return
Alarm
Netw fault
Alarm
20
Limit values
DIR
Parameters for limiting values
Range
Default setting
Project setting
Suction pressure
Psuc low alarm
bar (a)
0,30 … ?
3,00
Low warning
bar
+
0,00 … 3,00
0,20
Low limit
bar
+
0,00 … 3,00
0,50
Decr limit
bar
+
0,00 … 3,00
0,30
Psuc hi alm n1
bar (a)
0,30 … ?
6,50
Psuc hi alm n2
bar (a)
0,30 … ?
6,50
High warning
bar
-
0,00 … 3,00
0,20
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......