2.7.2
Compressor motor alarms
2.7.2.1
’Motor feedback’ alarm — start up of compressor motor takes too long
Output — compressor motor on
’Motor feedback’ signal equals 1
’Motor feedback’ timer active
’Time before motor feedback too long’
alarm generated
Figure 2.15, Compressor motor start without (A) and with (B) an alarm
A..
Normal case:
Compressor motor start without an alarm.
B..
In case of an alarm:
During the starting operation, the motor feedback signal is delayed for too long
and an alarm is generated.
•
If
(1)
Output — compressor motor on equals 1
→
Then
(3)
Start ’Motor feedback’
timer
•
If
(1)
Output — compressor motor on equals 1
and
•
If
(2)
’Motor feedback’ signal equals 0
and
•
If
(3)
’Motor feedback’
timer expired
→
Then
(4)
’Time before motor feedback too long’ alarm generated
2.7.2.2
’Feedback from motor starter missing’ alarm
Output — compressor motor on
’Motor feedback’ signal equals 1
’Feedback from motor starter missing’
alarm generated
Figure 2.16, ’Feedback from motor starter missing’ alarm
•
If
(1)
Output — compressor motor on
and
•
If
(2)
’Motor feedback’ signal equals 0
→
Then
(3)
’Feedback from motor starter missing’ alarm generated
Summary of Contents for Grasso
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ......
Page 95: ......
Page 96: ......
Page 98: ......
Page 109: ......
Page 110: ......
Page 112: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 138: ......
Page 147: ......
Page 148: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 164: ......
Page 165: ...02 04 Master_Backpage doc 1 ...
Page 166: ......