Prerequisites
●
The valve has been removed, see
.
●
Insert V-ring without grease. To facilitate fitting, use water with a drop of wash-
ing-up liquid to remove the surface tension. To ensure that no rust is transfer-
red, the washing-up liquid solution must be mixed in a ceramic, plastic, or stain-
less steel container.
Tools
●
V-ring insertion tool
CAUTION
Sharp-edged tool
Risk of injury if the pickset tool slips when removing the V-ring.
●
Clamp the valve disk with the vice mount into the vice.
INFO
Functional and running surfaces of the valves may not be damaged.
INFO
Do not grease the V-ring.
1.
Put a tool from the pickset into the V-
ring and take it out.
2.
Before mounting, wet the V-ring on the side not in contact with product (rear
side). Ensure that water does not drip into the V-ring groove on the valve disk.
3.
Air out the valve upon connection (22).
4.
Insert the V-ring. Make sure the instal-
lation position of the V-ring is correct.
9.7 Maintenance - 79 / 106
Summary of Contents for ECOVENT N ECO Series
Page 6: ...6 106 Table of Contents 0000000576 001 EN GB...
Page 9: ...1 4 Declarations of conformity 1 4 Declarations of conformity 9 106...
Page 12: ...12 106 1 4 Declarations of conformity 0000000576 001 EN GB...
Page 20: ...20 106 2 10 Emergency measures 0000000576 001 EN GB...
Page 38: ...38 106 5 6 Electrical connection with T VIS control top 0000000576 001 EN GB...
Page 42: ...42 106 7 2 Shutdown 0000000576 001 EN GB...
Page 82: ...82 106 9 7 Maintenance 0000000576 001 EN GB...
Page 84: ...84 106 9 7 Maintenance 0000000576 001 EN GB...
Page 98: ...98 106 12 2 Spare parts lists 0000000576 001 EN GB...
Page 103: ...2 20 10 2022 221MBL003579DE_4 13 2 Dimensions sheet Actuator ECO E 103 106...