8-12
T35 Transformer Protection System
GE Multilin
8.2 CYBERSENTRY
8 SECURITY
8
General Security Settings
Confirm RADIUS
Authentication
(Shared) Secret
Confirmation of the shared secret. The
entry displays as asterisks.
See the
following
password
section for
requirements
245 characters
N/A
-
Administrator
SETTING NAME
DESCRIPTION
MIN
MAX
DEFAULT UNITS MINIMUM
PERMISSION
Session Lockout
Number of failed authentications before the
device blocks subsequent authentication
attempts for the lockout period
0 (lockout
disabled)
99
3
-
Administrator
Session Lockout
Period
The period in minutes that a user is prevented
from logging in after being locked out
0 (no period) 9999
3
min
Administrator
Syslog Server IP
Address
The IP address of the target Syslog server to
which all security events are transmitted
0.0.0.0
223.255.
255.254
0.0.0.0
-
Administrator
Syslog Server Port
Number
The UDP port number of the target syslog server
to which all security events are transmitted
1
65535
514
-
Administrator
Local Authentication When enabled, local authentication with roles is
allowed. When disabled, the UR only
authenticates to the AAA server (RADIUS).
NOTE:
Administrator and Supervisor (if still
enabled) remain active even after local
authentication is disabled. The only permission
for local Administrator is to re-enable local
authentication when local authentication is
disabled. To re-enable local authentication, the
Supervisor unlocks the device for setting
changes, and then the Administrator can re-
enable local authentication.
Disabled
Enabled
Enabled
-
Administrator
Firmware Locked
Indicates if the device receives firmware
upgrades. If Yes and the firmware upgrade
attempt is made, the device denies the upgrade
and displays an error message that the lock is
set. On each firmware upgrade, this setting goes
back to the default.
No
Yes
Yes
-
Administrator
Factory Service
Mode
When enabled (checkbox selected), the device
can go into factory service mode. To enable,
Supervisor authentication is necessary.
Disabled
Enabled
Disabled
-
Supervisor
(Administrator
when Supervisor
is disabled)
Restore to Defaults Sets the device to factory defaults
No
Yes
No
-
Administrator
Supervisor role
When enabled (checkbox selected), the
Supervisor role is active. To enable,
Administrator authentication is necessary. When
disabled, the Supervisor role is inactive. To
disable, Supervisor authentication is necessary.
Disabled
Enabled
Enabled
-
Administrator to
enable and
Supervisor to
disable
RADIUS user
names
Ensure that RADIUS user names are not the
same as local role names
See RADIUS
server
documents
See
RADIUS
server
documents
-
Administrator
Password
Local roles except for Observer are password-
protected. All RADIUS users are password-
protected.
See the
following
password
section for
requirements
See the
following
password
section for
requireme
nts
Change
Me1#
Text
The specified role
and Administrator,
except for
Supervisor, where
it is only itself
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...