![GE T35 UR Series Instruction Manual Download Page 260](http://html.mh-extra.com/html/ge/t35-ur-series/t35-ur-series_instruction-manual_130382260.webp)
5-138
T35 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
,
(EQ 5.29)
where:
T
= operate time (in seconds),
TDM
= Multiplier setting,
I
= input current,
I
pickup
= Pickup Current setting,
K
,
E
=
constants,
t
r
= characteristic constant, and
T
RESET
= reset time in seconds (assuming energy capacity is 100%
and
RESET
is “Timed”)
Table 5–17: IEC (BS) INVERSE TIME CURVE CONSTANTS
IEC (BS) CURVE SHAPE
K
E
T
R
IEC Curve A (BS142)
0.140
0.020
9.7
IEC Curve B (BS142)
13.500
1.000
43.2
IEC Curve C (BS142)
80.000
2.000
58.2
IEC Short Inverse
0.050
0.040
0.500
Table 5–18: IEC CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
(TDM)
CURRENT (
I
/
I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
IEC CURVE A
0.05
0.860
0.501
0.315
0.249
0.214
0.192
0.176
0.165
0.156
0.149
0.10
1.719
1.003
0.630
0.498
0.428
0.384
0.353
0.330
0.312
0.297
0.20
3.439
2.006
1.260
0.996
0.856
0.767
0.706
0.659
0.623
0.594
0.40
6.878
4.012
2.521
1.992
1.712
1.535
1.411
1.319
1.247
1.188
0.60
10.317
6.017
3.781
2.988
2.568
2.302
2.117
1.978
1.870
1.782
0.80
13.755
8.023
5.042
3.984
3.424
3.070
2.822
2.637
2.493
2.376
1.00
17.194
10.029
6.302
4.980
4.280
3.837
3.528
3.297
3.116
2.971
IEC CURVE B
0.05
1.350
0.675
0.338
0.225
0.169
0.135
0.113
0.096
0.084
0.075
0.10
2.700
1.350
0.675
0.450
0.338
0.270
0.225
0.193
0.169
0.150
0.20
5.400
2.700
1.350
0.900
0.675
0.540
0.450
0.386
0.338
0.300
0.40
10.800
5.400
2.700
1.800
1.350
1.080
0.900
0.771
0.675
0.600
0.60
16.200
8.100
4.050
2.700
2.025
1.620
1.350
1.157
1.013
0.900
0.80
21.600
10.800
5.400
3.600
2.700
2.160
1.800
1.543
1.350
1.200
1.00
27.000
13.500
6.750
4.500
3.375
2.700
2.250
1.929
1.688
1.500
IEC CURVE C
0.05
3.200
1.333
0.500
0.267
0.167
0.114
0.083
0.063
0.050
0.040
0.10
6.400
2.667
1.000
0.533
0.333
0.229
0.167
0.127
0.100
0.081
0.20
12.800
5.333
2.000
1.067
0.667
0.457
0.333
0.254
0.200
0.162
0.40
25.600
10.667
4.000
2.133
1.333
0.914
0.667
0.508
0.400
0.323
0.60
38.400
16.000
6.000
3.200
2.000
1.371
1.000
0.762
0.600
0.485
0.80
51.200
21.333
8.000
4.267
2.667
1.829
1.333
1.016
0.800
0.646
1.00
64.000
26.667
10.000
5.333
3.333
2.286
1.667
1.270
1.000
0.808
IEC SHORT TIME
0.05
0.153
0.089
0.056
0.044
0.038
0.034
0.031
0.029
0.027
0.026
0.10
0.306
0.178
0.111
0.088
0.075
0.067
0.062
0.058
0.054
0.052
0.20
0.612
0.356
0.223
0.175
0.150
0.135
0.124
0.115
0.109
0.104
0.40
1.223
0.711
0.445
0.351
0.301
0.269
0.247
0.231
0.218
0.207
0.60
1.835
1.067
0.668
0.526
0.451
0.404
0.371
0.346
0.327
0.311
0.80
2.446
1.423
0.890
0.702
0.602
0.538
0.494
0.461
0.435
0.415
1.00
3.058
1.778
1.113
0.877
0.752
0.673
0.618
0.576
0.544
0.518
T
TDM
K
I I
pickup
⁄
(
)
E
1
–
---------------------------------------
×
=
T
RESET
TDM
t
r
1
I I
pickup
⁄
(
)
2
–
---------------------------------------
×
=
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...