5-128
T35 Transformer Protection System
GE Multilin
5.5 FLEXLOGIC
5 SETTINGS
5
5.5.7 NON-VOLATILE LATCHES
PATH: SETTINGS
FLEXLOGIC
NON-VOLATILE LATCHES
LATCH 1(16)
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
•
LATCH 1 TYPE
: This setting characterizes Latch 1 to be Set- or Reset-dominant.
•
LATCH 1 SET
: If asserted, the specified FlexLogic operands 'sets' Latch 1.
•
LATCH 1 RESET
: If asserted, the specified FlexLogic operand 'resets' Latch 1.
Figure 5–44: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC
LATCH 1
LATCH 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LATCH 1 TYPE:
Reset Dominant
Range: Reset Dominant, Set Dominant
MESSAGE
LATCH 1 SET:
Off
Range: FlexLogic operand
MESSAGE
LATCH 1 RESET:
Off
Range: FlexLogic operand
MESSAGE
LATCH 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LATCH 1
EVENTS: Disabled
Range: Disabled, Enabled
842005A3.CDR
LATCH 1 FUNCTION:
LATCH 1 TYPE:
LATCH 1 SET:
LATCH 1 RESET:
RUN
SET
RESET
SETTING
SETTING
SETTING
SETTING
FLEXLOGIC OPERANDS
Off=0
Off=0
Enabled=1
LATCH 1 ON
LATCH 1 OFF
LATCH N
TYPE
LATCH N
SET
LATCH N
RESET
LATCH N
ON
LATCH N
OFF
Reset
Dominant
ON
OFF
ON
OFF
OFF
OFF
Previous
State
Previous
State
ON
ON
OFF
ON
OFF
ON
OFF
ON
Set
Dominant
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
Previous
State
Previous
State
OFF
ON
OFF
ON
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...