These instructions apply to bolt-on circuit breaker kits with 
catalog numbers AMCB6FGB and AMCB4FGB. 

These kits are for use with circuit breaker types FGH, FGL, 
FGN, and FGP. 

Use circuit breaker cover kit catalog number AFP4FGD. 

Installation 

 

 

 

WARNING: 

Danger of electrical shock or injury. 

Turn

 

OFF power ahead of the panelboard or 

switchboard before working inside the equipment 
or removing any component

Equipment is to be 

installed and maintained by properly trained and 
qualified personnel only. 

 

 

  1.  Confirm the contents of the kit.

 These kits are used to 

install double-branch FG-frame Record Plus™ circuit 
breakers into Spectra APNB bolt-on interiors. The 
vertical space required for each kit is 5.50 inches (4X). 

 

 

Figure 1 illustrates the parts included in this kit, which 
are listed in Table 1. 

 

  In the following instructions, numbers in brackets in the 

text and figures refer to the items in Table 1. 

 

 

Figure 1. Parts included in the bolt-on circuit breaker kits 

AMCB4FGB and AMCB6FGB. 

Application 

Ces instructions s’appliquent à des kits de disjoncteurs 
boulonnés ayant les numéros de catalogue AMCB6FGB et 
AMCB4FGB. 

Ces kits sont pour utilisation  de disjoncteurs de types FGH, 
FGL, FGN, et FGP. 

Utiliser le kit de couvercle de disjoncteur de numéro de 
catalogue AFP4FGD. 

Installation 

 

 

AVERTISSEMENT: 

Danger de choc électrique ou 

de blessure. Mettre le courant en avant du panneau 
de distribution ou du tableau de contrôle à Off 
avant de travailler à l’intérieur de l’équipement ou 
d’en retirer toute composante. L’équipement ne doit 
être installé et entretenu que par du personnel 
correctement formé et qualifié. 

 

 

  1. Confirmer le contenu de ce kit.

 Ces kits sont utilisés 

pour installer des disjoncteurs Record Plus™ à cadre FG 
dans des intérieurs boulonnés Spectra APNB. L’espace 
vertical requis pour chaque kit est de 5.50 pouces (4X). 

 

 

La Figure 1 illustre les pièces incluses  dans ce kit, 
lesquelles sont listées à la Table 1. 

 

  Les numéros entre crochets dans le texte et les figures des 

instructions qui suivent réfèrent aux items de la Table 1. 

 

Figure1. Pièces incluses dans les kits de disjoncteurs 

boulonnés AMCB4FGB et AMCB6FGB. 

Spectra Series™ Power Panelboards 
Panneaux de distribution Spectra Series™ 

Bolt-On Circuit Breaker Kits 
Kits de disjoncteurs boulonnés 

 

DEH40420 Installation 

Instructions 

R02 

 

Instructions d’installation 

DEH41047 Installation 

Instructions 

R02 

 Instructions 

d’installation 

Summary of Contents for Spectra Series AMCB6FGB

Page 1: ...ue AMCB6FGB et AMCB4FGB Ces kits sont pour utilisation de disjoncteurs de types FGH FGL FGN et FGP Utiliser le kit de couvercle de disjoncteur de numéro de catalogue AFP4FGD Installation AVERTISSEMENT Danger de choc électrique ou de blessure Mettre le courant en avant du panneau de distribution ou du tableau de contrôle à Off avant de travailler à l intérieur de l équipement ou d en retirer toute ...

Page 2: ...ste des pièces pour les kits AMCB4FGB et AMCB6FGB 2 Locate the side of the interior with a 2 75 inch reference distance The circuit breaker straps are mounted on the side of the panel interior bus at which the distance from the vertical bus face to the inner face of the bus support rail is 2 75 inches as indicated in Figure 2 3 Assemble antiturn clips onto carriage bolts Slide an antiturn clip 4 o...

Page 3: ...ight Go to step 6 to install the mounting brackets G9 Figure 9 Installing the straps for three phase connections isometric view Figure 9 Vue isométrique de l installation des brides pour des connexions trois phases La Figure 5 illustre les configurations possibles de courroies de barre omnibus pour les étapes suivantes 4 Installations trois phases Utiliser la procédure suivante pour toutes les ins...

Page 4: ...ble bus strap combinations Figure 5 Combinaisons possibles de brides de barre omnibus 5 Two pole installations Use the following procedure for all two pole installations kit AMCB4FGB For installations using phases A and B continue with step 5a For installations using phases A and C go to step 5c For installations using phases B and C go to step 5e 5 Installations deux pôles Utiliser la procédure s...

Page 5: ...lages de boulon de carrosserie sur des phases A et B Positionner les assemblages de boulon de carrosserie 14 et de clip immobilisé 4 tel que montré aux Figures 10 et 11 Figure 11 Installing carriage bolt assemblies on phases A and B isometric view Figure 11 Vue isométrique d assemblage de boulons de carrosserie sur des phases A et B 5b Installer les brides sur des phases A et B Placer les brides d...

Page 6: ...A et C Placer les brides de cadre FG 5 sur les boulons de carrosserie et les clips immobilisés tel que montré aux Figures 16 et 17 Placer les rondelles cuvettes 7 sur les boulons et fixer avec des écrous 11 Serrer les connexions à la main Aller à l étape 6 pour installer les supports de fixation Figure 17 Installing straps on phases A and C isometric view Figure 17 Vue isométrique de l installatio...

Page 7: ...rail latéral du panneau avec des vis auto taraudeuses 1 tel que montré à la Figure 22 Serrer les vis à 30 po lb 7 Installer les disjoncteurs Positionner la barrière par dessus le support de fixation tel que montré à la Figure 23 Positionner les disjoncteurs de manière à ce que les terminaux du côté ligne ou On reposent sur les blocs de contact sous jacents des brides et que les côtés opposés soien...

Page 8: ...l autre dérivation laissée ouverte pour future utilisation En ce cas isoler les surfaces exposées des blocs de contact des brides dans la dérivation inutilisée Couvrir les surfaces de contact avec deux couches de ruban thermoplastique reconnu UL 105 C OANZ2 tel que Permacel P 30 105 ou 3M 66R afin d obtenir une épaisseur minimale d isolation de 0 013 pouce These instructions do not cover all detai...

Reviews: