Page 22
LOCATION 47
AUXILIARY OUTPUT #1, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 1.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 1, Location 46). Programming a "0" makes the output follow the event.
LOCATION 48
AUXILIARY OUTPUT #2, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 2.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 2, Location 46). Programming a "0" makes the output follow the event.
LOCATION 49
AUXILIARY OUTPUT #3, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 3.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 3, Location 46). Programming a "0" makes the output follow the event.
LOCATION 50
AUXILIARY OUTPUT #4, EVENT AND TIME
2 segments, numerical data
Segment 1
Use Table 2.1 to select the event that will activate Auxiliary Output 4.
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on data programmed in
Segment 4, Location 46). Programming a "0" makes the output follow the event.
AUXILIARY OUTPUT EVENT SELECTION
Table 2.1
DATA
EVENT
DATA
EVENT
DATA
EVENT
0
/
Burglary Alarm
19
Exit
38
Download In Process
1
/
Fire Alarm
20
Entry or Exit
39
Smoke Power
2
/
24 Hour Alarm
21
Armed State
40
Short Circuit (Over-
current)
3
/
Trouble Alarm
22
Disarmed State
41
Box Tamper
4
/
Tamper Alarm
23
Ready
42
Siren Tamper
5
Yelping Siren (Burglary)
24
Not Ready
43
Any Open
6
Temporal Siren (Fire)
25
Fire
44
Any Short
7
Any Siren
26
Fire Trouble
45
Any Fault (Open/ Short on
Non-Fire Zone)
8
Any Bypass
27
Chime
46
/
Any Alarm
9
AC Fail
28
/
Expander Trouble
47
Beeping Keypad
10
Low Battery
29
Dynamic Battery Test Time
48
/
Code Entry (See note)
11
/
Duress
30
Open Period
49
˜
/
Key FOB Function 1
12
/
Aux 1 Keypad Zone
31
Closed Period
50
˜
/
Key FOB Function 2
13
/
Aux 2 Keypad Zone
32
Listen-In
51
/
Always On
14
/
Panic Keypad Zone
33
Line Seizure
52
Flashing in Alarm
15
Keypad Tamper
34
Ground Start
53
Armed AWAY
16
/
Autotest
35
Fail To Communicate
54
Armed STAY
17
Alarm Memory
36
Telephone Line Fault
18
Entry
37
Program Mode
˜
Events 49 & 50 require NX-408E, NX-416E, or NX-448E wireless receivers to operate.
/
If set to follow condition, these events will be 1 second.
NOTES:
When Event 48 is programmed, it is possible to program a user code's authorization to select which output(s) a
particular code will activate. When LED 8 is on for an authorization, then LEDs 1- 4 correspond to that code activating
outputs 1 - 4 respectively.
(See programming the LED keypads on page 8.)